The Apollo XP95 I.S. Heat Detector is an intrinsically safe fire detection device designed specifically for use in hazardous environments where explosive gases or vapours may be present. Using a single thermistor sensor, the detector continuously monitors ambient temperature and provides a count output proportional to the external air temperature, offering reliable heat detection across a wide temperature range.

Featuring BASEEFA and IECEx certification with Ex ia IIC T4/T5 GA classification, this detector is ideal for challenging industrial environments that are dirty or smoky under normal circumstances. The device is unaffected by wind or atmospheric pressure, making it suitable for demanding applications where traditional detectors may struggle.

Compatible with Apollo’s XP95 protocol and Discovery and CoreProtocol systems, the detector offers seamless integration into existing fire alarm infrastructures. The intrinsically safe design ensures safe operation in potentially explosive atmospheres whilst maintaining the reliability and performance expected from the Apollo XP95 range.

Features

  • Intrinsically safe certification for use in hazardous areas (BASEEFA and IECEx certified)
  • Linear temperature approximation over the range 25°C to 90°C with 1°C per count resolution
  • Single NTC thermistor sensor for accurate temperature monitoring
  • Continuous sampling frequency for rapid response to temperature changes
  • XP95 native digital communication compatible with Discovery and CoreProtocol systems
  • Two-wire supply configuration (polarity sensitive) for simplified installation
  • Low power consumption with 150 µA quiescent current
  • Red LED alarm indicator with optional remote LED capability
  • Wide operating temperature range from -20°C to +60°C
  • IP44 rated protection against dust and water ingress
  • White flame retardant polycarbonate housing with low air flow resistance design
  • Compact dimensions: 100mm diameter x 42mm height
  • Ideal for environments that are dirty or smoky under normal circumstances
  • Unaffected by wind or atmospheric pressure variations
  • Complies with EMC Directive, ATEX Directive, Marine Equipment Directive and Construction Products Regulation

FAQ

What is an intrinsically safe heat detector?

An intrinsically safe heat detector is designed for use in hazardous environments where explosive gases or vapours may be present. The XP95 I.S. Heat Detector is certified to Ex ia IIC standards, meaning it limits electrical energy to levels that cannot cause ignition, even in the event of a fault. This makes it suitable for installation in potentially explosive atmospheres such as oil refineries, chemical plants, and offshore platforms.

How does the XP95 I.S. Heat Detector work?

The detector uses a single NTC (Negative Temperature Coefficient) thermistor sensor to continuously monitor ambient temperature. The thermistor provides a voltage output proportional to the external air temperature, which is converted to a digital count value. The detector provides linear approximation over the temperature range of 25°C to 90°C, with a resolution of 1°C per count, enabling accurate temperature monitoring and fire detection.

How many I.S. detectors can be fitted to a circuit?

The number of intrinsically safe detectors that can be installed on a circuit depends on the safety barrier type and the devices fitted. Typically, an I.S. circuit will have a maximum load of 20 detectors. However, this is restricted to 12 optical detectors in an IIC environment. The exact number also depends on how many detector LEDs are allowed to illuminate concurrently by the control and indicating equipment (CIE).

Can I connect a remote LED indicator to this detector?

Yes, the XP95 I.S. Heat Detector has a dedicated drive point (+R terminal) for connecting a remote LED indicator. The remote LED must be a standard high-efficiency red LED and does not require a series limiting resistor as the current is internally limited to approximately 500 µA. The Apollo MiniDisc Remote Indicator (Part No. 53832-070) is suitable for use with this detector. Unlike the standard XP95 range, the remote LED operates in series with the integral LED.

What is the operating temperature range?

The XP95 I.S. Heat Detector has two operating temperature ranges depending on the T-rating: -20°C to +45°C for T5 classification, and -20°C to +60°C for T4 classification. The guaranteed temperature range is -20°C to +60°C. The detector can be stored at temperatures from -30°C to +80°C.

Is this detector suitable for smoky environments?

Yes, the XP95 I.S. Heat Detector is specifically designed for environments that are dirty or smoky under normal circumstances. Unlike optical smoke detectors, heat detectors are not affected by ambient smoke, dust, or particles in the air, making them ideal for industrial environments, kitchens, workshops, and other areas where smoke or dust is regularly present.

What fire alarm systems is this detector compatible with?

The XP95 I.S. Heat Detector features XP95 native digital communication and is compatible with Apollo Discovery and CoreProtocol systems. It connects to a two-wire loop circuit carrying both data and 14V to 22V DC supply, allowing for addressable fire detection with full integration into compatible control panels.

What certifications does this detector hold?

The detector holds multiple international certifications including BASEEFA (BAS02ATEX1289X) and IECEx (IECExBAS12.0091X) for intrinsically safe operation. It complies with the ATEX Directive 2014/34/EU, EMC Directive 2014/30/EU, Marine Equipment Directive 2014/90/EU, and Construction Products Regulation (EU) 305/2011. It also meets EN 54-5 standards for vibration, impact and shock testing.

Specifications

  • Part Number: 55000-440APO
  • Detection Principle: Linear approximation over temperature range 25°C to 90°C
  • Sensor: Single NTC thermistor
  • Sampling Frequency: Continuous
  • Sensitivity: 25°C to 90°C: 1°C/count (-20°C returns 8 counts)
  • Supply Wiring: Two wire supply, polarity sensitive
  • Terminal Functions L1: Positive supply
  • Terminal Functions L2: Negative supply and remote LED negative
  • Terminal Functions +R: Remote LED positive
  • Supply Voltage: 14V – 22V DC
  • Quiescent Current: 150 µA
  • Power-Up Surge Current: 1mA
  • Duration Of Power-Up Surge Current: 0.3 seconds
  • Max Power-Up Time: 4 seconds
  • Analogue Value At 25°C: 25 ± 5 counts
  • Alarm Indicator: Red light emitting diode (LED)
  • Alarm LED Current: 700 µA
  • Remote LED Current: 500 µA (internally limited)
  • Input Capacitance: 3.3 nF
  • Storage Temperature: -30°C to +80°C
  • Operating Temperature: -20°C to +45°C (T5), -20°C to +60°C (T4)
  • Guaranteed Temperature Range: -20°C to +60°C
  • Humidity: 0% to 95% RH
  • Vibration, Impact & Shock: To EN 54-5
  • IP Rating: IP 44
  • BASEEFA Certificate No: BAS02ATEX1289X
  • IECEx Certificate No: IECExBAS12.0091X
  • Classification (Max Ambient): Ex ia IIC T4 GA (≤ +60°C), Ex ia IIC T5 GA (≤ +45°C)
  • Dimensions: 100mm diameter x 42mm height
  • Weight: 105g
  • Material Housing: White flame retardant polycarbonate
  • Material Terminals: Nickel plated stainless steel
  • Digital Communication: XP95 native, Compatible with Discovery and CoreProtocol
  • Compliance: EMC Directive 2014/30/EU, Construction Products Regulation (EU) 305/2011, Marine Equipment Directive 2014/90/EU, ATEX Directive 2014/34/EU