Haydon

Haydon HAY-PSUEN54-5A EN54-4 Power Supply | 24V DC, 5A, Small Enclosure

£127.45 (inc VAT: £152.94)

Low Stock

SKU: HAY-PSUEN54-5A Category: Brand:

You may also need

Key features

  • Five-code amber diagnostic LED for fault finding
  • 5A continuous output for larger auxiliary loads
  • Separate GEN and EPS volt-free fault outputs

Downloads

Summary

The Haydon HAY-PSUEN54-5A is a 27.6VDC uninterruptible power supply built to feed auxiliary devices on a fire alarm system, and what sets it apart on the bench is its built-in diagnostic LED, which gives you five distinct fault codes rather than a single generic warning light. That means you can read the amber LED and know straight away whether you’re looking at a blown fuse, a missing battery, a charging fault or a failed temperature sensor.

View full overview Show less

On a commercial install that saves you a return visit and gives you something concrete to report back to the client or main contractor. You get the diagnosis on site, first time, instead of swapping parts to find the fault by elimination.

Inside the small steel enclosure the unit houses 2 x 7Ah batteries and switches to battery standby automatically if mains power is lost, maintaining output to keep connected fire devices running. Two-stage charging and temperature-compensated charging voltage keep those batteries in good condition between services, so you’re not called back for premature battery failure.

Features

  • 5A rated output - power a larger run of auxiliary fire devices from a single PSU
  • Amber diagnostic LED - five fault codes let you pinpoint the issue on site without test gear
  • GEN and EPS volt-free outputs - report general fault and mains loss status back to a panel or BMS
  • Two-stage battery charging - bulk charges to 80% within 24 hours then floats to 100% within 48 hours
  • Deep discharge protection - disconnects batteries below 21V to prevent damage from over-draining
  • Overload protection circuit - protects the PCB from damage during a short circuit or overload on the output
  • Temperature-compensated charging - adjusts charging voltage with ambient temperature to extend battery life
  • Compliant to EN54-4:1997+A1+A2 for use on fire detection and alarm systems

Specifications

Rated Voltage Frequency110-240V AC, 47-63Hz
Input Current1.2A
Mains Fuse RatingF3A
Output Voltage Mains Power22.0-27.6 Vdc
Output Voltage Battery Standby20.0-26.0 Vdc
Ripple<150 mV
Output FuseF5A
Battery FuseF5A
Imax With Charging5A
Imax No Charging5.8A
Battery Capacity2 x 7Ah
Ri Max5Ω maximum internal resistance of battery and circuitry
I Min0.1A
Battery ChargingTwo stage - bulk charge to 80% within 24 hours, float charge to 100% within 48 hours
Constant Current Charge0.8A
Temperature Compensation-30mV/°C (0-50°C)
Low Battery Voltage Trigger23V
Deep Discharge Protection Cut Out21V
GEN Fault OutputNormally closed, 0.50A @ 60Vdc, 0.9Ω solid state relay, volt free; opens if mains failed and battery under 23V, or fault condition
EPS Fault OutputNormally closed, 0.50A @ 60Vdc, 0.9Ω solid state relay, volt free; opens if loss of mains for over 10 seconds
Operating Temperature-20°C to +45°C, 20-90% RH non-condensing
Storage Temperature-25°C to +85°C, 10-90% RH non-condensing
Enclosure Material1.2mm steel, white powder coated
Enclosure Dimensions WxHxD275 x 330 x 80mm
Weight Excluding Batteries3.3kg
Weight With Batteries FittedApproximately 8kg
ApprovalsEN54-4:1997+A1+A2, EMC 2014/30/EU, LVD 2014/35/EU, RoHS2.0 2011/65/EU, Environmental Class II

FAQ

What battery capacity does the HAY-PSUEN54-5A take?

This model is built for the small enclosure and houses 2 x 7Ah sealed lead acid batteries connected in series using the supplied bridging wire. If your standby time calculation needs more capacity than 7Ah batteries can provide, you’ll need to check whether a larger enclosure variant suits the job instead.


Can the GEN and EPS outputs be wired into a 230V circuit?

No. The datasheet specifies these are volt-free relay contacts rated 0.50A at 60Vdc, so any circuit you connect them to must stay below 60Vdc.


Why is the yellow fault LED still flashing after I've powered it up?

On initial power-up with no batteries or temperature sensor connected, the yellow fault LED will flash continuously - this is expected and not a fault. Once the batteries and temperature sensor leads are connected and the system is retested, the LED should stop flashing after a few seconds.


What cable size should I use for the output wiring?

Haydon’s recommended minimum for the 5A output PSU is 0.75mm² cable, with earth fitted if required. Mains cable should also be a minimum of 0.75mm² with an earth connection.


How do I know if the batteries are correctly connected during commissioning?

Disconnect one of the battery leads and the yellow fault LED should begin flashing within a minute, with the amber diagnostic LED showing two flashes as per the fault-finding guide. Reconnect the batteries and both LEDs should stop flashing after a few seconds, confirming correct connection.


Does this unit need a dedicated mains supply?

Yes, the PSU should be connected to a dedicated mains circuit with a Mains Isolation Switch labelled ‘FIRE ALARM - MAINS POWER ISOLATION SWITCH’, fused at a maximum of 5 amps.


Downloads

Additional information

Output Current

5A

Device Type

Battery Charging

Yes

Maximum Batteries

2 × 7Ah

Colour

Mounting

Surface

Fault Relay / LED

Trade
Account
Enquiry?