C-TEC BF430C/CC ActiV Conventional Wall Sounder 100dB(A), Red, Shallow or Deep Base

SKU: C-TEC-BF430C-CC-master-sku
SKU: C-TEC-BF430C-CC-master-sku Category: Brand:

Key features

  • 100dB(A) output at 1m
  • 31 selectable tones, two volume levels
  • Shallow IP21C or deep IP33C base

Downloads

Summary

The C-TEC BF430C/CC ActiV is a red conventional wall sounder with a nominal 100dB(A) output at 1 metre. Manufactured in the UK and LPCB certified to EN54-3, it offers 31 selectable primary tones, an optional secondary tone and high or low volume settings.

View full overview Show less

Choose the shallow-base BF430C/CC/SR for indoor use, or the deep-base BF430C/CC/DR for installations including covered outdoor areas. Both operate from 18–30V DC and draw a typical 4mA at 30V DC, with a maximum alarm current of 6mA at that voltage.

Features

  • 100dB(A) nominal output: Audible warning at 1 metre, with high and low volume settings
  • 31 primary tones: Select an alarm tone to suit the system, with an optional secondary tone
  • Low current demand: Typical 4mA and maximum 6mA alarm current at 30V DC
  • LPCB certification: Third-party certified to EN54-3 for fire alarm sounders
  • Shallow or deep base: IP21C shallow version for indoor use; IP33C deep version suitable for covered outdoor areas
  • Conventional panel compatibility: Compatible with C-TEC CFP, FP, MFP and EP203 panels; test compatibility with third-party panels before use
  • 18–30V DC operation: For compatible conventional fire alarm sounder circuits
  • UK manufacture: Produced by C-TEC in a red housing

Specifications

SpecificationShallow baseDeep base
Part numberBF430C/CC/SRBF430C/CC/DR
BaseShallowDeep
ManufacturerC-TECC-TEC
RangeActiVActiV
Device typeConventional wall sounderConventional wall sounder
ColourRedRed
CertificationLPCB certified to EN54-3LPCB certified to EN54-3
Operating voltage18–30V DC18–30V DC
Nominal sound output100dB(A) at 1m100dB(A) at 1m
Primary tones31 selectable tones31 selectable tones
Secondary toneOptionalOptional
Volume settingsHigh / lowHigh / low
Typical alarm current4mA at 30V DC4mA at 30V DC
Maximum alarm current6mA at 30V DC6mA at 30V DC
IP ratingIP21C (Type A)IP33C (Type B)
ApplicationWall mounted; indoor onlyWall mounted; suitable for covered outdoor areas
Dimensions108mm diameter × 99mm deep114mm diameter × 132mm deep
Weight215g315g
Operating temperature−10°C to +55°C−10°C to +55°C
Maximum humidity95% RH, non-condensing95% RH, non-condensing
Visual alarm / flashNoneNone

FAQ

What is the difference between the shallow and deep base versions?

BF430C/CC/SR has an IP21C shallow base for indoor use. BF430C/CC/DR has an IP33C deep base and can be used in covered outdoor areas. The deep version is larger and heavier.


Does this sounder include a beacon or VAD?

No. These BF430C/CC models provide an audible alarm only, with no visual alarm or flash.


Which fire alarm panels are compatible?

C-TEC lists compatibility with its CFP, FP, MFP and EP203 conventional panels and virtually all other makes. Testing on third-party panels is recommended before use.


How many tones and volume settings are available?

There are 31 selectable primary tones, an optional secondary tone, and high or low volume settings.


What current should I allow for sounder-circuit calculations?

At 30V DC, C-TEC specifies a typical alarm current of 4mA and a maximum of 6mA. Use the relevant maximum rating and account for the rest of the circuit when checking the system design.


Is the deep base suitable for exposed outdoor locations?

C-TEC specifies covered outdoor areas for the IP33C deep-base version. Do not treat it as a fully weatherproof sounder for exposed locations.