VoCALL Emergency Assist Standalone Disabled Toilet Kit
Summary
The Eaton Emergency Assist Alarm Stand Alone Kit (CFEAPULLKIT) provides the perfect solution for conformity with Building Regulations Document M and Equality Act 2010. This comprehensive kit has been specifically designed to meet the needs of disabled service users and conforms to all relevant requirements including Disability Rights Commission code of practice, English Tourism Council Recommendations and RNIB signage guidelines.
The system is a simple 2 wire installation that uses combined high output blue LED indication and buzzer to ensure response to emergency calls. The kit comprises all components needed to install a fully compliant emergency assistance system, with additional parts available separately for system flexibility. The design incorporates high contrast printing for increased visibility and tactile braille signage to assist partially sighted people in easily operating the cancel plate, ensuring full accessibility compliance.
Features
- Complies with regulations and recommendations including BS8300
- Dual loop pull cord for reliable operation
- High contrast labels for improved visibility
- Blue LED indication with audible buzzer
- Quick and simple installation with limited cabling requirements
- High contrast printing for increased visibility
- Tactile braille signage for partially sighted users
- Additional plate can be added for system flexibility
- 2 wire system design for installation simplicity
- Complete kit with all necessary components included
- Low current power supply unit included
- Over door indicator with visual and audible signals
- Cancel button with braille signage
- Pull cord accessory pack included
- Disabled stickers included (pack of 5)
FAQ
What components are included in the CFEAPULLKIT?
The complete kit includes: Emergency assist pull cord unit (CFEAPULL), Low current power supply unit (CFEAPSUKIT), Over door indicator (CFEAODI), Cancel button (CFEARSP), Pull cord accessory pack (CFEACORD), and Disabled sticker pack of 5 (CFEADS).
Where should the pull cord be positioned for accessibility compliance?
The upper cord pull should be located between 800mm and 1000mm above floor level, while the lower cord pull should be exactly 100mm above floor level. The ceiling pull should be positioned so it’s readily accessible from the WC or bath. Knot the cord to ensure the lowest ring is 100mm from the floor and cut off excess cord.
How should the cancel button be positioned?
The cancel button should be positioned so that it is reachable from both the WC and from a wheelchair. This ensures accessibility for all users and compliance with Building Regulations Document M requirements.
What are the power supply requirements for the system?
The system requires a 12V power supply unit which should be fed from an isolating switched fused spur, fused at 3A. The mains supply should use fixed wiring with three core cable of no less than 1mm². The power supply unit should be situated in the corridor and appropriately marked and secure from unauthorised operation.
What cable requirements are needed for installation?
The system requires minimum 2 core 0.4mm² cable for the ELV wiring. Always segregate low voltage wiring from mains wiring. The circuit should be one continuous radial type circuit with no spurs, and is limited to one additional item from the Over Door Indicator, Pull Cord or Cancel units only.
How does the system operate during an emergency?
To place a call, operate the pull cord – LEDs will illuminate in the pull cord unit, cancel unit and over door indicator, with an internal buzzer sounding in the over door indicator. In normal state, the power supply unit power LED is lit. To reset the call, press the cancel button.
What standards does the system comply with?
The system should be installed in accordance with BS8300 recommendations and Building Regulations Approved Document M requirements. It conforms to Disability Rights Commission code of practice, English Tourism Council Recommendations, RNIB signage guidelines, and Equality Act 2010.
Specifications
- Complete Kit Part Number : CFEAPULLKIT
- System Type : 2 wire system
- Power Supply Voltage : 12V
- Mains Supply Fuse Rating : 3A
- Minimum Cable Requirement : 2 core 0.4mm²
- Mains Cable Requirement : 3 core minimum 1mm²
- Pull Cord Part Number : CFEAPULL
- Power Supply Unit Part Number : CFEAPSUKIT
- Over Door Indicator Part Number : CFEAODI
- Cancel Button Part Number : CFEARSP
- Pull Cord Accessory Pack Part Number : CFEACORD
- Disabled Sticker Pack Part Number : CFEADS
- Upper Cord Pull Height : 800mm to 1000mm above floor
- Lower Cord Pull Height : 100mm above floor level
- Installation Type : Continuous radial circuit with no spurs
- Maximum Additional Items : 1 additional item per circuit
- Compliance Standards : BS8300, Building Regulations Document M, Equality Act 2010
- Additional Compliance : Disability Rights Commission, English Tourism Council, RNIB guidelines