Summary

The AirSense ModuLaser Minimum Display Module is a scalable aspirating smoke detection solution designed to simplify installation and maintenance while extending the capabilities of traditional air sampling detectors. The system consists of display and detector modules, which communicate via RS-485 interconnections. The Minimum Display Module offers a cost-effective alternative to the Standard Display Module, featuring only status LEDs to indicate faults or alarms, which can also be reported via relay outputs or APIC.

ModuLaser is ideal for use in hostile environments due to its advanced features that resist dust and dirt. Its forward scattering optical detection provides early warning capabilities without nuisance alarms, and its environmental compensation technology ensures high reliability. This makes ModuLaser a perfect solution for environments that would disable other smoke detectors.

Features

  • Modular design for efficient zoning
  • Zoned aspirating smoke detection
  • Simplified installation with docking station
  • Quick fit pipe adaptor system
  • Universal status LEDs

Specifications

  • Physical Dimensions : 110.5 x 133.5 x 300 mm (4.35 x 5.25 x 11.8 in)
  • Status Indication : LED’s
  • Alarm Levels : 4, Aux, Pre-alarm, Alarm and Alarm 2
  • Net Weight : Display Module: 1.18 Kg (2.6 lb.), Detector Module: 1.57 Kg (3.46 lb.)
  • Event Log : 20,000 events per module
  • Colour : Cream
  • RS485 Support : Yes (SenseNET and SenseNET+)
  • Mounting Type : Surface mount
  • Connectivity : USB (x2), IP and APIC on Display Module
  • Cable Entries : 2 at the bottom, 2 at the rear, 2 at the top on Detector Module, and 3 at the top on the Display Module
  • Operating Voltage : 18 to 30 VDC
  • Cable Entry Size : 20 mm (0.5 in), top and bottom
  • Current Consumption : Display Module (at 24 VDC): 204 mA (Minimum), 232 mA (Standard), 232 mA (Command); Detector Module (at 24 VDC): 260 mA (fan speed 1), 380 mA (fan speed 6, default), 940 mA (fan speed 16)
  • Detector Module Orientation : Vertical, 0 or 180°
  • Operating Temperature : Equipment: -20 to +60 °C (-4 to +140 °F), Sampled air: -20 to +60 °C (-4 to +140 °F)
  • Detection Principle : Laser light scattering mass detection and particle evaluation
  • Particle Sensitivity Range : 0.003 to 10 microns
  • Relative Humidity : 0 to 95% noncondensing
  • Environment : Indoor
  • IP Rating : IP40
  • Sampling Pipe Length : Up to 250 m (820 ft.) combined per detector module
  • Regulatory Compliance : REACH, RoHS
  • Certification : BOSEC, CPR, CSIRO, EN54-20, LPCB, VdS
  • Quantity Sampling Holes : Up to 20 – Class A per detector module, Up to 40 – Class B per detector module, Up to 50 – Class C per detector module
  • Chart Recorder Inlet Size : 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Sampling Period : Adjustable between 1 s and 60 s
  • Inlet Location : Top or bottom
  • Capacity : 1 month @ 1 s / Up to 5 years @ 60 s
  • Exhaust Size : 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Exhaust Location : Top or bottom
  • Inlet Quantity : 1 per detector module
  • Input Quantity : 2 per module
  • Input Type and Rating : Supervised
  • Termination : 15 KΩ 5% 1/4 W
  • Programmable : Yes
  • Output Quantity : 3 per module
  • Output Type and Rating : Voltage free (contact rating 2 A at 30 VDC / NO/NC/C)