Advanced 4 Way Sounder Splitter Card
£110.11 (inc VAT: £132.13)
Summary
The Advanced Sounder Splitter Card is a peripheral unit designed specifically for use with all MxPro 5 control panels. This versatile expansion device takes a standard sounder circuit from either a control panel or other panel-based sounder circuit controller and effectively multiplies it to provide up to 4 monitored outputs, significantly expanding the capability of your fire alarm system.
In operation, the additional outputs mirror the behaviour of the input circuit they are connected to, ensuring synchronized operation across all connected devices. The card features comprehensive monitoring for both open and short circuit conditions, providing reliable fault detection capabilities. The unit can accommodate an independent power supply to deliver up to 1A per circuit, making it suitable for demanding applications requiring multiple sounder circuits.
Supplied as a PCB-only format for flexible mounting options, this cost-effective solution provides an economical alternative to additional ancillary hardware when expanding sounder circuit capacity in fire alarm installations.
Features
- 4 monitored sounder outputs with full fault detection
- Up to 1 Amp per circuit capacity
- Comprehensive monitoring for open and short circuit conditions
- Cost effective expansion solution
- Compatible with all MxPro 5 control panels
- Independent power supply capability
- PCB only format for flexible mounting
- Red LED indicators for sounder activation
- Yellow LED indicators for fault conditions
- 3 year manufacturer warranty
- Synchronized operation across all outputs
- EOL resistor termination support
FAQ
What fire alarm panels is this sounder splitter compatible with?
The Sounder Splitter Card is compatible with all MxPro 5 control panels from Advanced.
How many sounder circuits can this card provide?
The card provides 4 monitored sounder outputs from a single input circuit.
What is the maximum current capacity per circuit?
Each circuit can handle up to 1 Amp, with options for either 1A total across all circuits or 4A when using an external power supply.
What type of monitoring does the card provide?
The card provides full monitoring for open circuit and short circuit conditions on all 4 outputs, with visual LED indication for both activation and fault states.
Is this product still available for purchase?
No, this product is marked as obsolete by Advanced. Contact your distributor for current alternative solutions.
How are the outputs powered?
The sounder outputs can be powered either by the input trigger circuit or by an external 24Vdc supply depending on the configuration chosen.
Specifications
- Sounder Input : IN+ and IN- connect to input trigger, OUT+ and OUT- connect to remainder of input circuit or 10KΩ EOL resistor
- On Board Indication : 4 red sounder LEDs for output activation, 4 yellow fault LEDs for circuit monitoring
- 1A Splitter Outputs : 4 monitored sounder circuits with 1A total maximum load
- 4A Splitter Outputs : 4 x 1A rated monitored sounder circuits
- Power Supply Card 1A Version : Quiescent 25mA, Driving 50mA
- Power Supply Card 4A Version : Quiescent 30mA, Driving 55mA
- Power Supply Sounder Outputs 1A : Provided by input trigger sounder circuit
- Power Supply Sounder Outputs 4A : External 24Vdc 4A supply required
- Compatibility : All MxPro 5 control panels
- Warranty : 3 years standard
- Format : PCB only for mounting
- Order Code : MXS-021
- Product Status : Obsolete