Unicorn Voice Distributed Amplifier Panel with EVC

This item is not available to purchase online. Please contact our sales team for more information.

Contact Us

SKU: ViUV-DAPT Category: Brand:

Summary

The Unicorn Voice Distributed Amplifier Panel (ViUV-DAP) is a unique distributed wall-mounted, panel-based voice alarm and fire telephone solution that is compliant to EN54-16. This system simplifies the specification and installation of voice alarm and fire telephone systems by offering a comprehensive one cabinet solution for distributed applications.

The Distributed Amplifier Panel is suitable for a wide range of applications, from small stand-alone buildings through to multi-storey and campus-style developments. The system is fully compatible with any fire alarm system, making it an ideal choice for both new installations and retrofit projects.

For smaller applications, the DAP can be utilised as a standalone V1 voice alarm system by adding a message module, and can be upgraded to a V2 system with the addition of a microphone for live announcements. For larger sites, when used with a master amplifier or desk microphone, the DAP allows for very large site coverage with each panel providing up to 4 amplifiers.

Features

  • Modern 2.8″ TFT touch screen user interface with intuitive icon-based controls
  • Unique 1st fix enclosure/2nd fix chassis design for easy installation
  • Optional integral EVC module for emergency voice communication
  • Efficient 25W/50W/100W Class D amplifier modules up to 400W per cabinet
  • 4 x audio panel outputs with individual amplifiers per output
  • Distributed digital network supporting up to 64 panels
  • 256 audio outputs across entire network
  • NAC/FAD output for VADs, vibrating pillows and visual alarm devices
  • Compatible with any fire alarm system
  • Standalone V1 voice alarm capability with optional message module
  • Upgradeable to V2 system with microphone addition
  • Dual redundant fault tolerant network with 6 audio channels and 2 EVC channels
  • Simultaneous broadcast of evacuate, alert messages and live announcements
  • Networking via copper, single-mode or multi-mode fibre
  • Emergency Voice Communication supporting up to 512 lines across network
  • Digital Signal Processor with parametric EQ and 11×10 audio matrix
  • Easy configuration via touch screen without need for PC
  • Hot swap standby amplifier capability
  • Individual amplifiers per loudspeaker output for acoustic equalisation
  • A/B speaker splitter module option for additional circuits

FAQ

Can the DAP be used as a standalone voice alarm system?

Yes, the DAP can be utilised as a standalone V1 voice alarm system suitable for smaller applications like shop units by adding a message module. It can also be upgraded to a V2 system with the addition of a microphone for live announcements.

What is the difference between the DAP and MAP systems?

The DAP (Distributed Amplifier Panel) features a 2.8″ touch screen and is designed for distributed applications, typically situated within riser cupboards or plant rooms. The DAP requires at least one Master Amplifier Panel (MAP/T) to provide EVC control functionality.

What networking options are available for the DAP?

Unicorn Voice can be networked using copper cable (up to 250m), single-mode fibre (up to 4km) or multi-mode fibre (up to 1.6km). This flexibility allows for copper within buildings and fibre for longer distances between buildings.

How many EVC lines does the DAP support?

The DAP-T variant provides 8 EVC lines per panel for fire telephone, disabled refuge and emergency assistance alarms. The total system capacity is 512 lines across the network.

What amplifier configurations are available?

The DAP can be configured with 25W, 50W or 100W Class D amplifier modules in dual or quad configurations, with a maximum of 400W per cabinet. A hot standby amplifier (100W) can also be specified.

Is the DAP suitable for large site applications?

Yes, when used with a master amplifier or desk microphone, the DAP allows for very large site coverage. Each panel can provide 4 amplifiers and is typically situated within a riser cupboard or plant room for distributed coverage.

Specifications

Power

  • AC Supply Voltage: 100-240V AC ± 10%
  • AC Supply Frequency: 50/60Hz
  • Battery Capacity: 2x 12V 7Ah, 12Ah, 17Ah, 24Ah VRSLA
  • Standby Time: Perform battery calculation using Unicorn Voice battery sizing calculator

Controls And Indications

  • Statutory Indicators: AC, DC, PSU Status, General CPU fault, VA EVC Status
  • Touchscreen: All controls via 2.8″ TFT touchscreen

Audio Inputs

  • BGM: 1
  • Front Panel Microphone: N/A
  • External Microphone: 1
  • Fire Input Opto-isolated Sounder Circuit: 4 (with optional pull up)
  • Reset Input: 1
  • Auxiliary Inputs: 4
  • Input Sensitivity: 0dBV
  • Max Input Level: +3dBV
  • EQ: 5 band parametric
  • Dynamics: Gate/Compressor/Limiter

Messages

  • Message Module: Fitted as an option for redundancy
  • Storage: 64 total messages (8 Evacuate, 8 Alert, 8 Test, 40 General purpose)
  • Format: 16-bit sample 32K WAV file (512kbs)
  • Storage Location: Monitored store held on Micro SD card

Amplification

  • Quantity: Up to 4
  • Power: 25W, 50W, 100W Type D
  • Max Power Per Panel: 400W
  • Efficiency: 25W/50W >85%, 100W >81%
  • Loudspeaker Line Monitoring: DC EOL resistor 22kΩ
  • Loudspeaker Voltage: 70V/100V
  • Frequency Response: 70Hz to 14kHz
  • SNR: >72dBA

Audio Output Processing

  • EQ: 7 band parametric
  • Dynamics: Compressor/Limiter

Outputs

  • Fault Relay: 1x Volt free NC, Com
  • Relay 1: Programmable Volt free NO, Com-Default Operation-VA
  • Relay 2: Programmable Volt free NO, Com-Default Operation-EVC

EVC Module (ViUV-DAP-T only)

  • Number Of EVC Lines: 8 per panel (512 lines total system capacity)
  • Cabling: 1 x 2 core 1.5mm screened fire rated
  • Line Monitoring: 10kΩ 0.5W resistor

Network

  • Max Number Of Amplifier Panels: 64
  • Channels: 6x Audio, 2x EVC
  • Max Distance Between Panels: Copper 250m, Single-mode fibre 4km, Multi-mode fibre 1.6km
  • Speed: 4.096 M Baud
  • Network Cables: Copper – 2x 2 core 1.5mm screened fire rated, Single-mode fibre – 9/125μm, Multi-mode fibre – 62.5/125μm

Environmental

  • Operating Temperature: -5°C to +40°C
  • Humidity Range: 0 to 80% non-condensing
  • Ingress Protection: IP3X
  • Back Box Finish: RAL 7026 Graphite Grey
  • Dimensions (H×W×D): 740mm × 500mm × 220mm
  • Entries: 30x knockouts top, 24x rear, 2x mains
  • Weight Without Batteries: Max 28KGs