Key features

  • Switches both live and neutral
  • Internal fuse accessed behind the cover
  • Indicator shows mains at the switched output

Downloads

Summary

The Zeta 400-210R and 400-210W provide key-operated, double-pole isolation of the mains supply to fire alarm control equipment. Both live and neutral are switched, with an internal fuse and an indicator showing mains present at the switched output.

View full overview Show less

Choose Red for 400-210R or White for 400-210W in the colour selector. Both versions are supplied in a standard single-gang enclosure with a backbox.

The key can be removed in either the on or off position, so you can retain control of switching access during maintenance. The cover must be removed to access the fuse; in the off position, the fuse is disconnected from the supply.

Specifications

Red Model400-210R (select Red)
White Model400-210W (select White)
Maximum Voltage250V AC, 50Hz
Switch Contact Rating4A at 250V AC, double pole
Switched ConductorsLive and neutral
Switch Surge Rating80A
Fuse4A fast, 5 x 20mm, as specified in the manufacturer’s installation guide
Key Number901
Key RemovalRemovable in both on and off positions
Fuse AccessCover removal required
Fuse In Off PositionDisconnected from the supply
Mains IndicationGreen LED indicating mains present at the switched output
Enclosure MaterialRoHS-compliant flame-retardant ABS plastic
Mounting FormatSingle-gang enclosure with backbox; preformed holes for surface or 20mm conduit-box mounting
Housing Dimensions86 x 86 x 56.5mm
Weight175g

Features

  • Controlled switching access - key-operated isolation, with the key removable in both on and off positions
  • Both supply conductors switched - double-pole operation switches live and neutral together
  • Protected fuse access - the enclosure cover must be removed to reach the internal fuse
  • Visible output indication - an LED indicates mains present at the switched output
  • Boxed installation - standard single-gang enclosure and backbox, with preformed holes for surface or 20mm conduit-box mounting

FAQ

Which colour option should I choose for 400-210R or 400-210W?

Select Red for 400-210R or White for 400-210W. The manufacturer’s guide covers both boxed, fused models with the same double-pole switching arrangement and 4A contact rating, so choose the housing colour required for your installation.


Is this for the panel mains supply or the detector loop?

This is a mains supply isolator for fire alarm control equipment. It switches the live and neutral mains conductors; it is not a detector-loop short-circuit isolator.


What fuse does the manufacturer's guide specify?

The installation guide specifies a 4A fast fuse measuring 5 x 20mm. It also gives a 4A switch contact rating at 250V AC, so a higher-rated fuse must not be taken as permission to increase the load beyond the contact rating.


Can the key be removed while the supply is on?

Yes. The key can be removed in both the on and off positions, allowing authorised staff to retain the key after setting the required switch position.


Does it come with a backbox, and how is it mounted?

Both versions are supplied in a complete single-gang enclosure with a backbox. The enclosure has preformed holes for surface or 20mm conduit-box mounting and can be accessed by rectangular surface trunking.


How should I interpret the old BS 5839 reference?

Zeta’s published guidance quotes BS 5839-1:2002, while the maker’s installation guide refers to the 2013 edition. BSI lists BS 5839-1:2025 as the current edition for non-domestic fire alarm systems. Those historical references do not establish compliance with the current edition; assess the complete installation against the applicable current requirements.