Key features

  • One addressable loop with up to 127 devices, subject to loop loading
  • Supports compatible Gent S-Quad and S-Cubed devices
  • USB commissioning and RS485 connection for repeat indicators

Downloads

Summary

The Honeywell Gent NANO-24 is a standalone single-loop addressable fire alarm panel for compatible Gent S-Quad and S-Cubed devices. The loop supports up to 127 addressable devices, subject to the device mix, electrical load and cable limits.

View full overview Show less

Honeywell specifies the LOW visual alarm device (VAD) setting for Nano systems. Check the device codes and loading tables in the Honeywell Gent Nano installation manual before selecting devices. The panel also has two conventional sounder circuits and supports up to four compatible RS485 repeat indicators.

Features

  • One addressable detection loop with up to 127 devices, subject to loop loading
  • Supports compatible Gent S-Quad and S-Cubed loop devices
  • LOW VAD setting for compatible visual alarm devices on Nano systems
  • Two conventional master alarm circuits
  • Separate fire and fault changeover relays rated at 1 A at 24 V DC
  • USB connection for the Nano commissioning tool
  • RS485 connection for up to four compatible repeat indicators
  • Backlit alphanumeric LCD

FAQs

Which devices can I use with the Gent NANO-24?

The panel supports compatible Gent S-Quad and S-Cubed devices. Check the device code in the installation manual. Its table sets different maximum quantities by device type, and Honeywell specifies the LOW VAD setting on Nano systems.

How many devices can I connect?

Honeywell specifies a maximum of 127 addressable devices on the loop. The actual capacity depends on the device mix, electrical load and cable limits.

What batteries does the NANO-24 use?

Honeywell specifies two 12 V 7 Ah batteries and lists them as supplied with the NANO-24. The quoted 24-hour standby is subject to the system’s battery standby calculation.

Can I connect a repeater?

Honeywell specifies up to four compatible repeat indicator panels via RS485. See page 21 of the installation manual for the connection and power requirements.

Where can I find the Gent Nano installation manual?

Use the Honeywell Gent Nano installation manual for loop loading, wiring, repeater connections and battery installation.

Specifications

  • Manufacturer and model Honeywell Gent NANO-24
  • Detection loops One addressable loop
  • Loop capacity Up to 127 addressable devices, subject to loading and cable limits
  • Mains supply 230 V AC
  • Battery specification Two 12 V 7 Ah batteries
  • Standby 24 hours subject to battery calculations
  • Enclosure dimensions (W × H × D) 347 × 419 × 85.5 mm
  • Display Backlit alphanumeric LCD with eight lines of 40 characters
  • Conventional sounder circuits Two master alarm circuits
  • Fire and fault relay contacts Changeover, 1 A at 24 V DC
  • Connections USB for commissioning, RS485 for repeat indicators, RS232 for printer
  • Cable entry Top and rear knockouts
  • Panel design standards Honeywell lists EN 54-2 and EN 54-4