The Scope Communications PageTek Pro 2L is an “Industrial Strength” paging transmitter specifically designed for professional fire and security systems installed in commercial and industrial premises. This sophisticated wireless communication system is primarily designed to alert the hearing impaired in the event of a fire or other emergency where an audible sounder is the normal means of indication, ensuring comprehensive safety coverage for all occupants regardless of hearing ability.

Fully compliant with the recommendations detailed in BS5839-1:2017 for alerting the hearing impaired to fire alarm activation, the PageTek Pro 2L represents cutting-edge technology in professional fire safety communications. The system can also be deployed in conjunction with security alarm panels to alert guards who might be located remote from the main premises, providing flexible emergency communication solutions across diverse operational scenarios.

Main users include factories, offices, universities, schools, hospitals, hotels and public buildings where reliable emergency communication is critical. The system features UHF radio frequencies for superior in-building propagation, comprehensive self-monitoring capabilities, and multiple prioritised fire inputs with fault indication interfaces. Optional LOCKDOWN messaging capability is available upon request, making the PageTek Pro 2L suitable for comprehensive emergency management requirements.

Repeating panel display on pager

If repeating the panel display on pagers is a requirement, the following table outlines which version of this transmitter should be ordered.

ManufacturerModelTypeProtocolRecommended Transmitter
A.R.M.NursecallSCOPEPTPRO/2L
ADTMX, MX2 & MZXFireMODULEPTPRO/2LM
Advanced ElectronicsMX4 & MX5FireMODULEPTPRO/2LM
Advanced ElectronicsMX-5010 & MX-5020Relay output onlyContact us for guidance
Aid CallCP5000MODULEPTPRO/2LM
Aid CallCP3399NursecallMODULEPTPRO/2LM
Aid CallTSPNursecallESPAPTPRO/2L
Aid CallTouchsafe Pro NursecallNursecallESPAPTPRO/2L
AmpacFirefinder BMSFireMODULEPTPRO/2LM
Aritech1801MODULEPTPRO/2LM
AritechAdvisorAcc Con/IntruderMODULEPTPRO/2LM
AtenaComlitFireESPAPTPRO/2L
AustcoNursecallMODULEPTPRO/2LM
AutronicaFireMODULEPTPRO/2LM
Call AidNursecallSCOPEPTPRO/2L
CassCompanion 95MODULEPTPRO/2LM
Castle Care-TechCastleIntruderRelay output onlyContact us for guidance
ChubbCare CallNursecallSCOPEPTPRO/2L
ChubbCompanionNursecallMODULEPTPRO/2LM
ChubbControl Master 380FireMODULEPTPRO/2LM
ChubbControl Master 600FireMODULEPTPRO/2LM
ChubbGuardallSecurityMODULEPTPRO/2LM
ComelitAtenaFireESPAPTPRO/2L
CooperCF3000FireESPAPTPRO/2L
Courtney-ThorneNursecallSCOPEPTPRO/2L
C-TECQuantecNursecallSCOPEPTPRO/2L
C-TECZFPFireMODULEPTPRO/2L
C-TECXFPRelay output onlyContact us for guidance
C-TEC800Relay output onlyContact us for guidance
C-TECCFPRelay output onlyContact us for guidance
CYGNUSSCOPEPTPRO/2L
Eatoni-on CompactNursecallRelay output onlyContact us for guidance
Eclipse NursecallNursecallSCOPEPTPRO/2L
Electro-DetectorsEDAFireSCOPEPTPRO/2L
Electro-DetectorsZerioFireSCOPEPTPRO/2L
Electro-DetectorsZerio PlusFireSCOPEPTPRO/2L
EMSIRISSCOPEPTPRO/2L
EMSFirecellFireMODULEPTPRO/2LM
EMSSmartCellFireRelay output onlyContact us for guidance
EuronovaSecurityMODULEPTPRO/2LM
Europlex3GSIntruderSCOPEPTPRO/2L
EzoneEzoneSCOPEPTPRO/2L
FikeQuadnet model 507-0001Relay output onlyContact us for guidance
GentVigilonFireMODULEPTPRO/2LM
GentVigilon CompactFireMODULEPTPRO/2LM
GentNanoFireMODULEPTPRO/2LM
GentSentriFireMODULEPTPRO/2LM
Guardian Staff SafetySecuritySCOPEPTPRO/2L
HaesEspritRelay output onlyContact us for guidance
HKCAll modelsSecurityRelay output onlyContact us for guidance
HochikiHFPFireMODULEPTPRO/2LM
HochikiHFP LatitudeFireMODULEPTPRO/2LM
HoneywellGalaxyIntruderMODULEPTPRO/2LM
HoneywellGalaxy Dimension GD520IntruderMODULEPTPRO/2LM
HoneywellGalaxy FlexIntruderRelay output onlyContact us for guidance
HoneywellFAAST FlexFireRelay output onlyContact us for guidance
HoneywellSMS SenTRIFireMODULEPTPRO/2LM
Inim PrevidiaRelay output onlyContact us for guidance
KentecSyncro / AS / LiteFireMODULEPTPRO/2LM
KentecTaktisFireMODULEPTPRO/2LM
Kidde (Thorne)VegaFireMODULEPTPRO/2LM
LismoreInterCall OneNursecallSCOPEPTPRO/2L
LismoreInterCall One ControllerNursecallSCOPEPTPRO/2L
LismoreInterCall L7700NursecallSCOPEPTPRO/2L
LismoreInterCall L7700 IP gatewayNursecallSCOPEPTPRO/2L
LismoreInterCall 600 / 700NursecallSCOPEPTPRO/2L
LismoreInterCall Touch 900NursecallSCOPEPTPRO/2L
MedicareNursecallSCOPEPTPRO/2L
MorleyZX Range Port BFireMODULEPTPRO/2LM
MorleyZX Range Port DFireMODULEPTPRO/2LM
MorleyDX RangeFireMODULEPTPRO/2LM
MorleyGL4-5SeFireMODULEPTPRO/2LM
MorleyMaxFireRelay output onlyContact us for guidance
MinvierM1000MODULEPTPRO/2LM
NotifierID-1000FireMODULEPTPRO/2LM
NotifierID-2000FireMODULEPTPRO/2LM
NotifierID-3000FireMODULEPTPRO/2LM
NotifierPearlFireMODULEPTPRO/2LM
NotifierXLS80eFireMODULEPTPRO/2LM
OnDisSmartShelfSecurityMODULEPTPRO/2LM
OrisecSecurityMODULEPTPRO/2LM
PacomIntruderSCOPEPTPRO/2L
PinpointSecuritySCOPEPTPRO/2L
Protec Fire Detection6300/6400/6500FireSCOPEPTPRO/2L
ProfileFireMODULEPTPRO/2LM
PyronixAll modelsRelay output onlyContact us for guidance
PSSFirequestFireSCOPEPTPRO/2L
SASSecuritySCOPEPTPRO/2L
ScantronicMultiscan (4660)Nursecall/SecSCOPEPTPRO/2L
SiemensCerberus ProFireESPAPTPRO/2L
SiemensSPCSecurityMODULEPTPRO/2LM
Static Systems (Codemlon)NursecallMODULEPTPRO/2LM
Static Systems900EVOFireRelay output onlyContact us for guidance
Static SystemsUltima Full IP RangeNursecallMODULEPTPRO/2LM
Technical Alarm SysSCOPEPTPRO/2L
Telealarm (Bosch)NursecallESPAPTPRO/2L
TelevicNursecallESPAPTPRO/2L
TexecomPremierIntruderMODULEPTPRO/2LM
Tyco/MinervaMX T2000FireMODULEPTPRO/2LM
Tyco/Minerva80IntruderMODULEPTPRO/2LM
Tyco/Control Equipment/ZettlerFireclassFireMODULEPTPRO/2LM
Tyco/ZettlerMX, MX2 & MZXFireMODULEPTPRO/2LM
Tyco/ZettlerMedicall 800NursecallSCOPEPTPRO/2L
VigilNurse Call systemNursecallCOMP2PTPRO/2L
Vox-ignisLexicomm ViLX-TMSSCOPEPTPRO/2L
VisonicSpiderSecuritySCOPEPTPRO/2L
Wandsworth (Aid-Call)NursecallESPAPTPRO/2L
Wandsworth PCNursecallESPAPTPRO/2L
ZettlerPR0885DFireMODULEPTPRO/2LM
ZettlerProfileFireMODULEPTPRO/2LM
Zeta AlarmsQuatroFireMODULEPTPRO/2LM
ZitonZP2FireMODULEPTPRO/2LM
ZitonZP3FireMODULEPTPRO/2LM

Features

  • UHF radio link technology for robust in-building coverage and superior propagation
  • Unique coding system provides minimum 2 million different codes, expandable to 16 million
  • Self-monitoring system with comprehensive diagnostics and fault detection
  • Rugged steel enclosure rated to IP54 for demanding industrial environments
  • Backlit 2-line text display continuously reports system status information
  • Additional visible and audible status indicators for comprehensive monitoring
  • Prioritised fire alarm inputs and fault inputs for emergency response hierarchy
  • Automated test calls alert pagers to loss of radio signal coverage
  • Fault notification to host control equipment via monitored interface link
  • Key-locked “System Test” function for routine system checking and maintenance
  • Over 90 hours operation from internal 12V 18Ah SLA battery backup
  • RS232 serial input for additional messaging and system integration
  • Optional Ethernet card and additional RS232 input for enhanced connectivity
  • High power 1W ERP RF transmitter for enhanced coverage of large sites
  • Multiple antenna options including 3/4 wave, Mini Dipole, and Folded Dipole
  • Compatible with Scope high integrity pagers featuring distinct vibrate patterns
  • Out of coverage alerts with “No Service” indication and 15-minute reminders
  • Monitored interface cable with “common fault” relay output to host panel
  • Compliance with Radio Equipment Directive 2014/53/EU and BS5839-1:2017
  • Optional LOCKDOWN messaging capability available upon request

FAQ

What is the primary purpose of the PageTek Pro 2L system?

The PageTek Pro 2L is primarily designed to alert hearing impaired individuals in commercial and industrial premises during fire or other emergencies where audible sounders are the normal means of indication. It ensures comprehensive safety coverage for all occupants regardless of hearing ability.

Which standards does the system comply with?

The system is designed to comply with BS5839-1:2017 recommendations for alerting the hearing impaired to fire alarm activation. It also meets Radio Equipment Directive 2014/53/EU, RoHS Directive 2015/863, and various EN standards including EN 300 224, EN 301 489-1, and IEC 62368-1:2020.

How does the unique coding prevent interference from neighbouring systems?

All Scope systems use coding which provides a minimum of 2 million different codes, expandable to 16 million using inherent features of Scope pagers. This prevents false triggering of pagers from neighbouring systems, especially important where multiple transmitters are installed on the same site.

What antenna options are available for different coverage requirements?

Three antenna options are available: 3/4 wave fixed antenna for most commercial sites, Mini Dipole antenna for larger sites or areas of difficult propagation, and Folded Dipole antenna for maximum coverage such as campuses and multi-building sites.

How does the system alert users when pagers go out of coverage?

If any Scope pager goes out of coverage, within two minutes the pager will vibrate until acknowledged and display a “No Service” message. The message remains on screen until the pager is back in service, with reminder vibrate alerts every 15 minutes as recommended in BS5839-1:2017.

What pager options are available with the system?

Available pagers include GEO 40A10 (alphanumeric, 2 line, 40 character), GEO 87Z (alphanumeric, 4/8 line zoom, 80/160 character), and EPOCSM (responder/paging transceiver with desktop charger). All feature distinct vibrate alerts for emergency messages and comprehensive status indication.

Specifications

  • Models: PTPRO/2L, PTPRO/2LM
  • Dimensions: 380* x 320 x 110mm (*840mm with 3/4 wave antenna)
  • Wall Mount Centres: 344 x 220mm, Hole Dia. 4.75mm
  • Clearance Requirements: Minimum 200mm all sides, plus 460mm on top if 3/4 wave antenna fitted
  • Power Input: 90-230V AC 50-60Hz, 10W maximum
  • Backup Supply: 12V 18Ah SLA battery (not supplied)
  • Battery Life: Over 90 hours operation
  • Facilities Required: Isolated 230V AC mains supply within 1 metre
  • Host Fire Panel: Within 1.5 metres of unit
  • RF Output: 1W ERP high power transmitter
  • Operating Frequency: UHF radio frequencies
  • Enclosure Rating: IP54 rugged steel enclosure
  • Display: Backlit 2 line text display
  • Communication: RS232 serial input, optional Ethernet card
  • Compliance: Radio Equipment Directive 2014/53/EU
  • Standards Applied: EN 300 224 V2.1.1 (Radio Paging), EN 301 489–1 V2.2.1 (EMC), IEC 62368-1:2020 (Safety)
  • Fire Safety Standard: BS 5839-1:2017, para 18 & Annex C
  • RoHS Compliance: RoHS Directive (EU) 2015/863
  • Antenna Options: LDPRO (Mini Dipole), 34BNC (3/4 wave fixed), FDANT (Folded Dipole)
  • Interface: Multiple prioritised Fire inputs and fault input
  • Monitoring: Self-monitoring system with comprehensive diagnostics
  • Licensing: Requires licence for operation in the UK