Shopping Basket

0 Items

Subtotal £0.00

Unicorn Voice Wall Microphone

This item is not available to purchase online. Please contact our sales team for more information.

Contact Us

SKU: ViUV-FMC Category: Brand:

Summary

The Unicorn Voice Fire Microphone (ViUV-FMC) is a unique distributed wall-mounted, panel-based voice alarm and fire telephone solution that simplifies the specification and installation of voice alarm systems. This EN54-16 compliant system offers a comprehensive one-cabinet solution comprising master amplifier panels, distributed amplifier panels, and advanced microphone controls.

Designed for versatility, the Unicorn Voice system is suitable for a wide range of applications from small standalone buildings through to multistorey and campus-style building complexes. The system is compatible with any fire alarm system and provides exceptional flexibility for both emergency and general paging requirements.

The intuitive 7″ TFT touch screen interface utilises icons wherever possible to simplify the user experience, whilst the automatic fire user login facility ensures immediate access during emergency situations without requiring password authentication.

Features

  • Modern 7″ TFT resistive touch screen user interface
  • Live and automated broadcast capabilities to specific zones or all-call basis
  • Automatic fire user login facility requiring no password
  • Optional EVC repeater functionality providing eight lines per panel
  • High quality robust microphone with advanced audio processing
  • Flexible configuration allowing local and site-wide control
  • Multiple user account levels with customisable permissions
  • Comprehensive logging functionality with micro SD card storage
  • Emergency and general paging options
  • 7-band parametric EQ and compressor/limiter audio processing
  • Up to 250m maximum distance between microphone and panels
  • Easy on-site configuration via touch screen without PC requirement
  • Fire telephone, disabled refuge and emergency assistance alarm capability
  • Aesthetically pleasing appearance with robust construction

FAQ

What is the maximum distance between the microphone and amplifier panels?

The maximum distance between the microphone and panels is 250m using copper cabling with the recommended 1x 2 core and 1x 4 core 1.5mm fire resistant cable.

How many microphones can be connected per amplifier panel?

Up to one microphone can be connected per master or distributed amplifier panel, providing multiple control points throughout the system.

Does the system require a password during fire emergencies?

No, the system features an automatic fire user login facility, meaning no password is required during emergency situations for immediate access to critical functions.

What user account levels are available?

The system supports multiple user accounts including Manager, Engineer, Fire User, Guest, and 7 additional customisable user levels, each with different permission settings.

Can the system be configured without a PC?

Yes, the entire system can be configured from one display position using the 7″ touch screen interface, eliminating the need for a PC during installation and setup.

What EVC functionality does the system provide?

When specified with an EVC module, the system provides eight lines per panel for fire telephone, disabled refuge and emergency assistance alarms, with location display prompting users to the nearest communication point.

Specifications

  • Power Supply Voltage: 24 VDC
  • Current Consumption: 130mA
  • Operating Temperature: -5°C to +40°C
  • Humidity Range: 0 to 80% non-condensing
  • Ingress Protection: IP3X
  • Dimensions (H×W×D): 300mm × 350mm × 90mm
  • Weight: 4.5Kg
  • Back Box Finish: RAL 7035 Grey
  • Trim Finish: Pantone-Process Black
  • Display: 7″ TFT resistive touchscreen
  • Audio Frequency Response: 300Hz to 12KHz
  • Audio Output Processing: 7 band parametric EQ
  • Audio Input Processing: 5 band parametric EQ
  • Dynamics Processing: Compressor/Limiter
  • Cable Type: 1x 2 core and 1x 4 core 1.5mm fire resistant cable
  • Maximum Cable Distance: 250m copper
  • Cable Entries: 2× rear cable entries, 14 x 20mm top
  • Microphones Per Panel: 1 maximum
  • Compliance: EN54-16
  • Part Code: ViUV-FMC

Downloads