Talentum IR2 Flame Detector (Ex d)

£1,700.00 (inc VAT: £2,040.00)

Low Stock

SKU: 16511-00 Category: Brand:

Summary

The Talentum® Flame Detector IR2 Ex d (Model 16511-00) is a specialized flame detection system designed specifically for hazardous areas where open fires may be expected. This flameproof detector is engineered to detect almost all flames, including hydrocarbon fires with 4.3 μm emissions through to invisible fires such as hydrogen, making it an essential safety device for high-risk industrial environments.

The detector utilizes advanced dual infrared sensor technology that responds to flickering, low frequency (1-15 Hz) infrared radiation emitted by flames during combustion. Its robust design ensures reliable operation even when the lens is contaminated by layers of oil, dust, water, vapour or ice. The two IR sensors respond to different IR wavelengths to effectively discriminate between genuine flames and spurious sources of radiation, while false alarms from flickering sunlight are avoided through a combination of filters and sophisticated signal processing techniques.

Certified to meet stringent international standards including EN54:10, LPCB, ATEX, and IECEx, the IR2 Ex d is approved for Category II 2 G D equipment in Zone 1, 2, 21 and 22 hazardous areas. The detector features a rugged copper-free aluminium alloy housing with IP66 rating, ensuring protection against dust and water ingress in demanding industrial applications.

Features

  • High immunity to false alarm sources through multi-spectrum detection
  • Tolerant of fumes, vapours, dust and mist contamination
  • Suitable for indoor areas with harsh environmental conditions
  • Detects flames through glass and transparent barriers
  • Unaffected by convection currents, draughts or wind
  • Proven response to multiple fuel types including n-heptane and methylated spirit
  • Selectable output options: relay contacts or 4-20 mA signal
  • Selectable response speed for different application requirements
  • Selectable sensitivity levels (High Class 1 and Low Class 3)
  • Built-in automatic and manual test functions
  • Low current consumption: 3-8 mA quiescent, 9-28 mA alarm
  • Fast response to fire: typically 4 seconds
  • 90° minimum cone field of view for wide area coverage
  • Operating temperature range from -10°C to +55°C
  • Programmable relay outputs with latching or non-latching operation
  • Three M20 cable gland entries for flexible installation
  • Compact dimensions: 158mm (H) x 149mm (W) x 134mm (D)

FAQs

What hazardous area zones is the Talentum IR2 Ex d approved for?

The detector is certified for Zone 1, 2, 21 and 22 hazardous areas. It carries ATEX certification as Category II 2 G D equipment and CENELEC/IEC approval as Ex db IIC T4 Gb (for gas) and Ex tb IIIC T135°C Db (for dust). This means it provides high-level protection suitable for areas where explosive atmospheres are likely to occur.

What is the detection range of the IR2 Ex d?

The detector offers two sensitivity settings: High sensitivity (Class 1) can detect a 0.1 m² n-heptane fire at 25 meters, while Low sensitivity (Class 3) can detect the same fire size at 12 meters. The device has been tested and approved at Class 1 performance level according to EN54-10 standards.

Can the detector operate in contaminated environments?

Yes, the IR2 Ex d is specifically designed to maintain detection capability even when the lens is contaminated by layers of oil, dust, water, vapour or ice. The detector is tolerant of fumes, vapours, dust and mist, making it particularly suitable for harsh industrial applications.

What types of flames can the detector identify?

The detector can identify almost all flame types, including visible hydrocarbon fires with 4.3 μm emissions and invisible fires such as hydrogen. It has been tested and approved for detection of both yellow flames (n-heptane) and clear flames (methylated spirit), demonstrating proven response to multiple fuel types.

How does the detector avoid false alarms?

The IR2 Ex d uses two IR sensors that respond to different infrared wavelengths (1.0 to 2.7 μm) to discriminate between genuine flames and spurious radiation sources. False alarms from flickering sunlight are avoided through a combination of optical filters and advanced signal processing techniques. The detector specifically responds to the low frequency flickering (1-15 Hz) characteristic of flames.

What output options are available?

The detector offers selectable output options as standard, including programmable relay contacts (rated at 48 Vdc, 0.75 A, 30 W for resistive loads) or 4-20 mA current loop signal. Relay operation can be configured for latching or non-latching behavior to suit different system requirements.

What power supply does the detector require?

The IR2 Ex d operates from a 14 to 30 VDC supply. Current consumption is low: 3-8 mA in quiescent mode (depending on relay configuration) and 9-28 mA during alarm conditions. The 24 Vdc supply line should be fused at 1 A.

What maintenance is required?

Regular maintenance checks should be performed at least annually, with frequency determined by environmental conditions. Maintenance includes cleaning external surfaces to prevent dust accumulation, checking flame path threads for corrosion, and verifying proper operation through built-in test functions. The detector features both automatic and manual test capabilities.

What cable glands should be used for installation?

For Zone 1, 2, 21 and 22 hazardous areas requiring IIC apparatus, Ex d barrier glands are mandatory. For Zone 2 and 22 areas requiring IIA and IIB apparatus, any Ex d gland is permitted. Cable glands must be certified and approved to meet EN 60079-14 standards, and should have IP66 rating or higher to maintain the enclosure’s IP rating.

Specifications

  • Model Number: 16511-00
  • Product Type: Conventional IR2 Flame Detector
  • Housing Material: Copper-free aluminium alloy (LM25)
  • Housing Colour: Red
  • Dimensions: 158mm (H) x 149mm (W) x 134mm (D)
  • Weight: 2.3 kg (5 lbs)
  • Cable Gland Entries: 3 x 20 mm (3 x ¾”)
  • Wiring: 1.0 to 4.0 mm² (12-18 AWG)
  • Supply Voltage: 14 to 30 VDC
  • Quiescent Current: 3-8 mA (depending on relay configuration)
  • Alarm Current: 9-28 mA (depending on relay configuration)
  • Power-up Time: 2 seconds maximum
  • Self-test Voltage: 14 to 30 VDC
  • Relay Maximum Ratings: 48 Vdc, 0.75 A, 30 W (resistive loads only)
  • Operating Temperature: -10°C to +55°C (+14°F to +131°F)
  • Storage Temperature: -20°C to +65°C (-4°F to +149°F)
  • Relative Humidity: 95% non-condensing
  • IP Rating: IP66
  • Detection Range High Sensitivity: 0.1 m² n-heptane at 25 m (Class 1)
  • Detection Range Low Sensitivity: 0.1 m² n-heptane at 12 m (Class 3)
  • Field Of View: 90° minimum cone
  • Operating Wavelength: 1.0 to 2.7 μm (IR)
  • Response Time: Typically 4 seconds
  • ATEX Certification: II 2 G D, Tamb -40°C to +85°C
  • CENELEC/IEC Gas Certification: Ex db IIC T4 Gb
  • CENELEC/IEC Dust Certification: Ex tb IIIC T135°C Db
  • Suitable Zones: Zone 1, 2, 21 and 22
  • Apparatus Certificate Numbers: Baseefa08ATEX0270, IECEx BAS08.0073
  • Standards Compliance: EN 60079-0, EN 60079-1, EN 60079-31, EN54-10, LPCB