The Nittan EV-Mini IP2 is a compact single input module with integral negative line short circuit isolator, designed for use with Nittan Evolution analogue addressable fire alarm systems. This sophisticated interface module provides the essential function of monitoring input signals from devices such as manual call points, aspirating smoke detectors, beam-type smoke detectors, ventilation control systems, and fire door control systems, transmitting their status to the control panel through the addressable loop.
Engineered for versatility and space efficiency, the EV-Mini IP2’s compact design makes it suitable for mounting within other fire detection equipment, eliminating the need for separate enclosures in many applications. The module fits comfortably inside standard UK 1-gang boxes (minimum 35mm depth) and can be integrated directly into devices such as aspirating smoke detectors or beam smoke detectors, with removable mounting tabs to facilitate installation in confined spaces.
The module provides one Class B input circuit that monitors devices with normally open dry contacts through a 10k ohm end-of-line (EOL) resistor. The EV-Mini IP2 continuously monitors the input circuit and reports the device status (normal, input, open circuit, or short circuit) to the control panel. A 470 or 680 ohm resistor is used to signal an alarm condition. The module features a constant current output (2.5mA typical) for connecting a remote LED indicator (such as the Nittan STA-R1), allowing visual status indication at remote locations.
The integral -ve line short circuit isolator is a critical safety feature that protects the entire fire alarm system. In the event of a short circuit between L+ and L- on the loop, the isolator automatically isolates the affected section of wiring, allowing devices on the opposite side of the short circuit to continue communicating with the control panel. A yellow LED on the module illuminates when the isolator is active, and the isolator automatically resets when the fault is cleared. The EV-Mini IP2 is certified to EN54-17:2005 for short circuit isolators and EN54-18:2005 for input/output devices, with CPR and UKCA compliance ensuring suitability for European and UK installations.
Features
- Single input module with integral -ve line short circuit isolator
- Compatible with Nittan Evolution analogue addressable system
- Compact size suitable for mounting within other equipment
- One Class B input circuit for monitoring normally open dry contacts
- 10k ohm EOL resistor for end-of-line supervision
- 470 or 680 ohm alarm resistor for input activation
- Monitors manual call points, aspirating detectors, beam detectors, and other devices
- Remote LED output for status indication at external locations
- Constant current output (2.5mA typ.) for remote indicator
- Compatible with Nittan STA-R1 remote LED indicator
- Address setting via EV-AD2-EXT handheld programmer
- Addressable from 1-254 (panel-dependent)
- Address programmable with or without power
- Micro USB connection for address programming
- Yellow LED indicates short circuit isolator activation
- Isolator automatically resets when fault clears
- Protects system while allowing opposite-side communication
- Fits inside UK 1-gang boxes (minimum 35mm depth)
- Removable mounting tabs for integration into other devices
- Suitable for aspirating smoke detectors and beam-type detectors
- Low quiescent current of 690 µA
- Alarm current 3.3 mA including LED
- Operating loop voltage 20 to 38 VDC
- Wide operating temperature range -10°C to +55°C
- Storage temperature range -40°C to +80°C
- Operates in humidity up to 95% RH non-condensing
- Cable terminals accept 0.75 to 2.5 mm² wire
- PC/ABS construction for durability
- Lightweight at 40 grams
- EN54-17:2005 / AC:2007 certified for short circuit isolators
- EN54-18:2005 / AC:2007 certified for input/output devices
- CPR Certificate 0905-CPR-00641
- UKCA Certificate 0359-UKCA-CPR-00010
- DoP Number 00641
- RoHS compliant for environmental responsibility
- Supplied with 10k EOL and 680 ohm alarm resistors
FAQs
What is the purpose of the EV-Mini IP2?
The EV-Mini IP2 is a single input interface module that allows normally open dry contact devices (such as manual call points, beam smoke detectors, aspirating smoke detectors, door monitoring switches, or other fire safety equipment) to be connected to Nittan Evolution analogue addressable fire alarm systems. The module monitors the input circuit and reports the device status to the control panel, enabling integration of non-addressable equipment into addressable fire alarm systems. This is essential for interfacing third-party equipment or conventional devices with modern addressable fire panels.
What does the integral short circuit isolator do?
The integral -ve line short circuit isolator is a critical safety feature that prevents a short circuit on one section of the loop from disabling the entire fire alarm system. If a short circuit occurs between L+ and L- (such as from damaged cable or water ingress), the isolator automatically disconnects the affected section of wiring. This allows devices on the opposite side of the fault to continue communicating with the control panel, maintaining partial system operation. A yellow LED on the module illuminates when the isolator is active, providing visual indication of the fault location. The isolator automatically resets once the short circuit is cleared.
How is the module address set?
The EV-Mini IP2 address is set using the Nittan EV-AD2-EXT handheld programmer. Connect the programmer to the module’s address setting port using a Micro USB cable, then use the programmer’s interface to change the address from the factory default of 1 to any address between 1-254 (depending on the control panel model’s capacity). Address setting can be performed with or without power applied to the module and even after the module has been connected to the loop. This flexibility simplifies commissioning and allows address changes without system disruption.
What resistor values are required for operation?
The EV-Mini IP2 requires two resistors for proper operation. A 10k ohm end-of-line (EOL) resistor is installed at the end of the input circuit to provide supervision and detect open circuits. When an alarm condition occurs (the monitored contact closes), a 470 or 680 ohm alarm resistor is connected across the input, signaling the alarm to the control panel. Both resistors are typically supplied with the module. The input circuit monitoring detects: alarm condition (less than 680 ohms), short circuit (less than 50 ohms), normal condition (10k ohm EOL present), and open circuit (greater than 20k ohms).
Can the EV-Mini IP2 be installed inside other equipment?
Yes, the EV-Mini IP2’s compact design (60.5mm x 48mm x 33mm) specifically allows installation within other fire detection equipment. It can be mounted inside aspirating smoke detector housings, beam-type smoke detector units, or integrated into manual call points. For installation inside UK 1-gang back boxes (minimum 35mm depth), use the mounting tabs provided. When installing inside aspirating or beam detectors, the mounting tabs can be removed to create an even more compact footprint. This integration capability simplifies installations by reducing the number of visible modules and enclosures required.
What is the remote LED output for?
The EV-Mini IP2 provides a constant current output (2.5mA typical) specifically designed to drive remote LED indicators such as the Nittan STA-R1. This allows installation of a visual indicator at a location separate from the module itself. For example, if the EV-Mini IP2 is mounted inside an aspirating smoke detector cabinet in a ceiling void, a remote LED indicator can be installed in a visible location to show when that input is in alarm. This provides valuable visual feedback for system status and alarm location identification without requiring access to the concealed module.
Is the EV-Mini IP2 compatible with all Nittan control panels?
The EV-Mini IP2 is compatible with Nittan Evolution analogue addressable fire alarm control panels. However, it is specifically NOT compatible with the Advanced MxPro4 (Mx4000) panel – for that panel, the Non-SCI model must be used instead. Before installation, verify compatibility with your specific control panel model. Additionally, note that it is not possible to mix +ve and -ve isolator styles on the same system, so ensure all isolators in your installation use the same polarity configuration as specified by the system design.
How do you install the module in a 1-gang back box?
To install the EV-Mini IP2 in a standard UK 1-gang back box (minimum 35mm depth), secure the module using the mounting tabs and appropriate screws. The compact dimensions allow it to fit comfortably within the back box along with the required wiring. Connect the loop wiring (from the panel or previous device, and to the next device) to the L+/L- terminals. Connect the input device wiring to the In+/In- terminals with the 10k ohm EOL resistor and alarm resistor (470 or 680 ohm) as shown in the wiring diagram. If using a remote LED indicator, connect it to the A+/A- terminals. Ensure all wiring conforms to BS5839 Part 1 and IEE wiring regulations.
What maintenance is required?
Inspection and testing of the EV-Mini IP2 should be carried out periodically according to BS 5839 Part 1 requirements or equivalent local codes of practice. For routine inspection, ensure the module is secure and undamaged, verify all wiring connections are tight, and check that the module responds correctly during system testing. When carrying out site testing, set the fire alarm control panel to test mode to prevent unwanted activation of alarm sounders and fire service summoning equipment. The module should be tested by activating the connected input device and verifying that the alarm is correctly reported at the control panel and that any remote LED indicator operates as expected.
What causes the yellow LED to illuminate?
The yellow LED on the EV-Mini IP2 illuminates when the short circuit isolator (SCI) is active. This occurs when the isolator detects a short circuit between L+ and L- on the loop wiring. The SCI automatically isolates the section of loop containing the short circuit, preventing the fault from disabling the entire system. The yellow LED provides immediate visual indication that the isolator has activated and helps technicians quickly locate which isolator has operated during fault-finding. Once the short circuit is cleared (by repairing the damaged cable or removing the fault condition), the isolator will automatically reset and the yellow LED will extinguish.
Specifications
- Model Number: EV-Mini IP2
- Part Number: F16-82250
- Product Type: Single input module with integral -ve line short circuit isolator
- Manufacturer: Nittan
- System Compatibility: Nittan Evolution analogue addressable systems only
- Operating Loop Voltage: 20 to 38 Vdc
- Quiescent Current: 690 µA
- Alarm Current: 3.3 mA (including LED)
- Current In Short Circuit: 15 mA
- Input: 1 x Class B
- Loop Resistance: < 50 ohm/km
- Input Line Resistance: < 50 ohm/km
- Eol Resistor: 10k ohm
- Input Alarm Resistance: 470 ohm or 680 ohm
- Input Threshold Alarm: < 680 ohm
- Input Threshold Short: < 50 ohm
- Input Threshold Open: > 20k ohm
- Remote Led Output Current: 2.5 mA typical (constant current)
- Address Range: 1 to 254 (panel dependent)
- Address Setting Method: EV-AD2-EXT handheld programmer via Micro USB
- Short Circuit Isolator Type: -ve line integral isolator
- Minimum Sw Open Voltage (vso Min): 11 Vdc
- Maximum Sw Open Voltage (vso Max): 14 Vdc
- Minimum Sw Close Voltage (vsc Min): 3 Vdc
- Maximum Sw Close Voltage (vsc Max): 10 Vdc
- Maximum Line Current (ic Max): 500 mA
- Maximum Switching Current (is Max): 1500 mA
- Maximum Leakage Current (il Max): 15 mA
- Maximum Switch Resistance (zc Max): 150 mΩ
- Isolator Led: Yellow (illuminates when SCI active)
- Isolator Reset: Automatic when fault clears
- Operating Temperature: -10°C to +55°C
- Storage Temperature: -40°C to +80°C
- Relative Humidity: < 95% RH (non-condensing)
- Cable Terminals: 0.75 to 2.5 mm²
- Wire Size Minimum: 0.75 mm²
- Wire Size Maximum: 2.5 mm²
- Material: PC/ABS
- Weight: 40 g
- Dimensions: 60.5mm (H) x 48mm (W) x 33mm (D)
- Dimensions (inches): 2.38″ (H) x 1.89″ (W) x 1.3″ (D)
- Mounting: Mounting tabs for 1-gang boxes, removable for equipment integration
- Minimum Box Depth: 35mm (for UK 1-gang boxes)
- Test Standards: EN54-17: 2005 / AC: 2007, EN54-18: 2005 / AC: 2007
- Cpr Certificate: 0905-CPR-00641
- Ukca Certificate: 0359-UKCA-CPR-00010
- Dop Number: 00641
- Rohs Compliant: Yes (EU Directive 2015/863)
- Compatible Remote Indicator: Nittan STA-R1
- Included Resistors: 10k ohm EOL x 1, 680 ohm alarm x 1
- Included Documentation: Installation manual
- Incompatibility Note: Not compatible with Advanced MxPro4 (Mx4000) Panel – use Non-SCI model
- Wiring Standards: IEE Wiring Regulations, BS5839 Part 1, or local national wiring regulations