VESDA VLP (LaserPLUS) Aspirating Smoke Detector
Obsolete
Summary
The VESDA VLP detector is the central element of the VESDA ASD product range, delivering very early warning smoke detection capabilities with an exceptional alarm sensitivity range of 0.005%–20% obscuration/m (0.0015%–6.25% obscuration/ft). Classified as a “Very Early Warning Smoke Detector”, the VLP detects fire at the earliest possible stage and reliably measures very low to extremely high concentrations of smoke.
Using unique detection principles and a stable Class 1 laser light source, the VLP employs advanced features including AutoLearn™ technology, VESDAnet™ communication, and referencing capabilities. The modular design allows for flexible installation options including recessed mounting, making it ideal for demanding commercial, industrial and critical infrastructure applications where early fire detection is paramount.
Features
- Wide sensitivity range
- Laser based smoke detection
- 4 configurable alarm levels
- High efficiency aspirator
- Four inlet pipes
- Airflow supervisor per sampling pipe
- Clean air barrier optics protection
- Easy to replace air filter
- 7 programmable relays
- VESDAnet™ communication
- AutoLearn™ technology
- Referencing capability
- Event log (up to 18,000 events)
- Modular design
- Recessed mounting option
- Stable Class 1 laser light source
- Ultra-fine air filtration
- Fault-tolerant communication protocol
FAQ
What is the sensitivity range of the VESDA VLP detector?
The VLP offers an alarm sensitivity range of 0.005%–20% obscuration/m (0.0015%–6.25% obscuration/ft), with four configurable alarm levels: Alert, Action, Fire 1, and Fire 2.
What area coverage can the VLP provide?
The VLP can typically cover up to 2,000 m² (21,520 sq.ft), depending on local codes and standards. Coverage is determined using the ASPIRE™ design tool for optimal pipe network configuration.
How many sampling pipes can be connected to the VLP?
The VLP supports four inlet pipes with a total aggregate pipe length of 200 m (656 ft) and maximum single length of 100 m (328 ft). Each pipe has individual airflow monitoring and supervision.
What is AutoLearn™ and how does it work?
AutoLearn™ monitors the ambient environment and automatically sets the most appropriate alarm thresholds during commissioning. It operates for a minimum of 15 minutes to a maximum of 15 days (recommended minimum 1 day) whilst maintaining pre-set threshold values.
What is the referencing feature and when is it used?
Referencing compensates for external pollution that may enter through “fresh air make up” in air handling systems. It ensures external pollution doesn’t interfere with true smoke level detection in the protected environment, preventing nuisance alarms.
What power requirements does the VLP have?
The VLP operates on 18-30 VDC supply voltage. Power consumption varies by aspirator speed: at 3000 rpm it consumes 5.8W quiescent/6.96W with alarm, whilst at 4200 rpm it consumes 8.16W quiescent/9.36W with alarm.
What communication options are available?
The VLP uses VESDAnet™, a fault-tolerant bi-directional communication protocol that allows continued operation during single point wiring failures. It enables system programming from a single location and supports the modular VESDA system architecture.
Specifications
- Supply Voltage : 18–30 VDC
- Power Consumption (3000 RPM Quiescent) : 5.8 W
- Power Consumption (3000 RPM With Alarm) : 6.96 W
- Power Consumption (4200 RPM Quiescent) : 8.16 W
- Power Consumption (4200 RPM With Alarm) : 9.36 W
- Current Consumption (3000 RPM Quiescent) : 240 mA
- Current Consumption (3000 RPM With Alarm) : 290 mA
- Current Consumption (4200 RPM Quiescent) : 340 mA
- Current Consumption (4200 RPM With Alarm) : 390 mA
- Dimensions (WHD) : 350 mm x 225 mm x 125 mm (13.8 in x 8.9 in x 4.9 in)
- Weight : 4.0 kg (9 lbs) including Display and Programmer modules
- IP Rating : IP30
- Operating Temperature (Tested) : -10°C to 55°C (14°F to 131°F)
- Operating Temperature (Detector Ambient) : 0°C to 39°C (32° to 103°F)
- Operating Temperature (Sampled Air) : -20° to 60°C (-4° to 140°F)
- Operating Humidity : 10%–95% RH, non-condensing
- Storage Temperature : 0° to 85° C
- Storage Humidity : Dry (<95%)
- Battery Life : Up to 2 years
- Aggregate Pipe Length : 200 m (656 ft)
- Maximum Single Pipe Length : 100 m (328 ft)
- Minimum Flow Per Pipe : 15 litres/min
- Area Coverage : Typically up to 2000 m² (21520 sq. ft.)
- Pipe External Diameter : 25 mm (1 in)
- Pipe Internal Diameter : 15–21 mm (9/16 in–7/8 in)
- Programmable Relays : 7 Relays, Contacts rated 2 A @ 30 VDC NO/NC Contacts
- Cable Access : 8 x 25 mm (1 in) knockouts in various positions
- Cable Termination : Screw terminals 0.2–2.5 sq mm (30–12 AWG)
- Alarm Sensitivity Range : 0.005%–20% obs/m (0.0016%–6.25% obs/ft)
- Alert Threshold Range : 0.005%–1.990% obs/m (0.0016%–0.6218% obs/ft)
- Action Threshold Range : 0.010%–1.995% obs/m (0.0031%–0.6234% obs/ft)
- Fire 1 Threshold Range : 0.015%–2.00% obs/m (0.0046%–0.625% obs/ft)
- Fire 2 Threshold Range : 0.020%–20.00% obs/m (0.0063%–6.25% obs/ft)
- Event Log Capacity : Up to 18,000 events stored on FIFO basis
- AutoLearn Duration : Minimum 15 minutes, maximum 15 days
- Pipe Modelling Design Tool : ASPIRE™
- Approvals : UL, ULC, FM, LPCB, VdS, CFE, ActivFire, NF-SSI, VNIIPO, CE, EN 54-20
- EN 54-20 Classifications : Class A (30 holes / 0.05% obs/m), Class B (60 holes / 0.06% obs/m), Class C (100 holes / 0.08% obs/m)
- Model Options : VLP-002 (two blank plates), VLP-012 (with LCD programmer), VLP-400 (with FOK)
- Manufacturer : Xtralis
Downloads
- Datasheet (Adobe PDF)
Additional information
| Weight | 4 kg |
|---|---|
| Indication | Fire & OK LEDs, Standard Display, LCD Programmer |