AirSense

AirSense 9-30501 MiniLaser Aspirating Smoke Detector | Laser Detection, High Sensitivity

£859.35 (inc VAT: £1,031.22)

Low Stock

SKU: 9-30501 Category: Brand:

You may also need

  • AirSense 9-30520 | MiniLaser Expansion Housing | Modular, 2-Module Slots, Flexible Mount

    In Stock

    £76.65 (inc VAT: £91.98)
    Add
  • AirSense 9-30521 | MiniLaser Input/Output Functional Module | 2 Programmable Inputs, 5 Relay Outputs

    In Stock

    £102.19 (inc VAT: £122.63)
    Add

Key features

  • Dip-switch or PipeCAD configuration
  • Up to two expansion modules
  • Bar graph smoke level display

Downloads

Summary

The AirSense MiniLaser (9-30501) is a compact, single-zone aspirating smoke detector (ASD) built for sites that need high-sensitivity, early-warning fire detection without a bulky footprint. Whether you’re protecting a server room, a heritage building or a compact plant space, it’s designed to draw air samples through a pipe network and detect incipient fires before they produce visible smoke.

View full overview Show less

For you on site, that means fewer callbacks for false alarms, faster commissioning, and a detector that scales from simple DIP-switch setups to more complex pipe designs without swapping hardware. The EN54-20 certification and CPR compliance also give you a straightforward story for sign-off on commercial fire installations.

It delivers this through laser-based forward-scattering detection paired with ClassiFire technology, which continuously adapts sensitivity to the environment to hold alarm stability over the product’s life. A docking station design keeps the sensitive electronics protected during first fix, and front-accessible wiring terminals let you test and maintain the unit live, without powering down or dismantling it.

Features

  • Dual configuration – set up simple pipe layouts with DIP-switches or model complex networks in PipeCAD from a laptop
  • Flexible module placement – fit the display and expansion sub-modules on either side of the detector to suit your wiring route
  • Up to two functional modules – add capacity in the expansion sub-module without a separate enclosure
  • Docking station design – remove the sensitive electronics during first fix so they aren’t damaged on site
  • Quick-fit pipe adaptor – locks down securely while leaving room for fast pipe connection and removal
  • Bar graph smoke display – gives an at-a-glance view of smoke level development alongside standard alarm and fault icons
  • ClassiFire adaptive sensitivity – continuously adjusts to environmental conditions to hold alarm stability and cut nuisance alarms
  • Continuous airflow monitoring – flags blocked sampling points, broken pipes and abnormal flow before they become a fault call
  • USB-C interface – handles advanced diagnostics, configuration and firmware updates from a laptop
  • Front-accessible wiring terminals – carry out live testing and maintenance without powering down or dismantling the detector
  • Embedded PipeCAD file storage – keeps the design on record even if the original documentation goes missing
  • 10/90 waste-gate airflow with multi-layer dust filter – protects the optical chamber and extends maintenance intervals
  • 20,000-event log and chart recorder – gives you long-term performance data for reporting and handover

FAQ

Can I commission the MiniLaser without a laptop?

Yes. For simple sampling pipe layouts, the DIP-switch interface lets you set key configuration on site without a PC. For more complex pipe networks, you’ll need PipeCAD modelling on a laptop connected via the USB-C port.


How many detection points can I run from a single unit?

The MiniLaser supports up to 125m of combined sampling pipe per detector module, with sampling hole counts of up to 10 for Class A, 20 for Class B or 35 for Class C, depending on the classification you’re designing to.


Can I add extra inputs or outputs later?

Yes. The expansion sub-module accepts up to two functional modules, such as the 9-30521 Input/Output functional module, and can be paired with the 9-30520 expansion housing if you need to add capacity beyond the base unit.


Is this detector suitable for outdoor or exposed locations?

No. The MiniLaser carries an IP40 rating and is specified for indoor use only, so it should be sited within a protected environment rather than exposed plant areas.


What certification does the MiniLaser hold?

It’s certified to EN54-20 and CPR compliant, which supports its use in commercial fire detection installations under BS 5839-1. Always confirm the specific pipe design and installation meet local approval requirements, as coverage area is subject to these.


Can I service the unit without powering it down?

Yes, all wiring terminals are front-accessible, so you can carry out live testing and routine maintenance without dismantling or de-energising the detector. For anything beyond routine checks, refer to the full installation and service manual.


Specifications

General

Status IndicationLEDs
User InterfaceAlarm and fault indicators, with smoke bar graph display
Alarm Levels4 (Aux, Pre-alarm, Alarm and Alarm 2)
Event Log20,000
ConnectivityUSB (USB-C)

Electrical

Operating Voltage18 to 30 VDC
Current Consumption120 mA – fan speed 1; 180 mA – fan speed 4 (default speed); 230 mA – fan speed 6; 365 mA – fan speed 10

Detection

Detection PrincipleLaser light scattering mass detection and particle evaluation
Sensitivity0.002 %obs/m to 25 %obs/m (0.0006 %obs/ft to 7.62 %obs/ft)
Coverage AreaUp to 1600m2 (subject to local approvals and installation standards)
Particle Sensitivity Range0.003 to 10 microns

Sampling Pipe

LengthUp to 125 m (410 ft.) combined per detector module
Quantity Sampling HolesUp to 10 – Class A per detector module; Up to 20 – Class B per detector module; Up to 35 – Class C per detector module
Inlet Size27 or 25 mm (1.06 or 0.98 in) outer diameter
Inlet LocationTop or bottom
Exhaust Size27 or 25 mm (1.06 or 0.98 in) outer diameter
Exhaust LocationTop or bottom
Inlet Quantity1

Input

Input Quantity1
Input Type And RatingSupervised
Termination15 KΩ 5% 1/4 W
ProgrammableYes

Output

Output Quantity3
Output Type And RatingVoltage free (contact rating 2 A at 30 VDC / NO/NC/C)
ProgrammableYes (2 x outputs / 1 x fixed for fault)

Physical

Physical Dimensions165 x 133.5 x 300 mm (6.5 x 5.25 x 11.8 in), W x D x H
Net Weight2.15 Kg (4.7 lb.)
ColourGrey-white (RAL 9002)
Mounting TypeDIN-rail, Surface mount
Cable Entries4 at the bottom, 2 at the rear, 5 at the top
Cable Entry Size20 mm (0.5 in) – top and bottom
Detector Module OrientationVertical (0 deg or 180 deg)

Environmental

Operating TemperatureEquipment: -10 to +60°C (14 to +140°F); Sampled air: -40 to +60°C (-40 to +140°F) with sampled air heated to operational temperature of at least -10°C (14°F)
Relative Humidity0 to 95% noncondensing
EnvironmentIndoor
IP RatingIP40

Regulatory

CompliancyREACH, RoHS
CertificationCPR, EN54-20

Chart Recorder

Sampling PeriodAdjustable between 1s and 60 s
Capacity1 month @ 1s / Up to 5 years @ 60 s
Values RecordedDetector value, 4 alarm level values, flow value and temperature (all simultaneously)

Compatible Products

MiniLaser Expansion Housing9-30520
MiniLaser Input/Output Functional Module9-30521

Downloads

Additional information

Weight2.15 kg
Device Type

Channels

Class A Holes

Class B Holes

Class C Holes

Pipework Diameter

,