Easy Relay 24V Fire Panel Relay (24V DC Coil)
£6.47 (inc VAT: £7.76)
Key features
- Two changeover contact sets
- Series diode for monitored bell circuits
- LED indicates active contacts
Downloads
Summary
The Easy Relay 24 (500-020) is a 24V DC coil relay for fire-system interfacing. It provides two changeover contact sets, allowing a panel trigger to operate a separate switched circuit.
View full overview Show less
T2 Solutions specifies a series diode in the coil circuit for connection to bell circuits using end-of-line (EOL) resistors. An LED indicates when the contacts are active; the installation guide includes a monitored-output wiring example.
This is the printed circuit board (PCB) version for mounting securely inside a suitable enclosure. Keep the 24V DC coil requirement separate from the contact switching rating when selecting it for your installation.
Read the Easy Relay 24 installation guide for terminal identification and the monitored-output connection example.
Specifications
| Model / Part Number | Easy Relay 24 / EASY RELAY24/PCB / 500-020 (shown as 500/020 in the guide) |
|---|---|
| Nominal Coil Input | 24V DC |
| Operational Current | 18mA at 24V DC |
| Coil Power | 0.4W |
| Drop-out Voltage | 3.5V DC |
| Contact Arrangement | Two changeover sets; double-pole, double-throw (DPDT) |
| Output Contact Rating | 230V AC, 8A maximum; 2000VA stated in the manufacturer guide |
| Contact Material | Silver alloy |
| Electrical Life | 100,000 operations at rated current |
| Operating Temperature | -40°C to +70°C |
| Indication | LED indicates contacts in the active position |
| Coil Circuit | Built-in series diode for bell circuits using end-of-line (EOL) resistors |
| Mounting | Secure PCB inside a suitable enclosure using at least one screw; fixing screw supplied |
| Dimensions | 52mm wide x 48mm long x 30mm high |
FAQ
Is 500-020 a 24V DC or 24V AC relay?
The 500-020 has a nominal 24V DC coil input. The 230V AC figure in its specifications is a contact switching rating, not the coil supply voltage.
Can I connect it to a monitored fire alarm output?
T2’s guide shows a fire-system monitored-output connection using an end-of-line (EOL) resistor. The relay includes a series diode in the coil circuit for this application. Check the panel manufacturer’s output requirements and available current against the relay’s 18mA draw at 24V DC, and follow the connection diagram.
Does the 8A rating mean the coil draws 8A?
No. The coil’s operational current is 18mA at 24V DC; 8A is the maximum contact switching current stated alongside 230V AC in T2’s guide. Check the switched load against the contact ratings separately from the panel output powering the coil.
Does this model need an enclosure?
Yes. T2 specifies that the printed circuit board (PCB) must be mounted securely inside a suitable enclosure using at least one fixing screw, which is supplied. The 500-020 is the PCB model; T2 separately lists 500-021 as its 24V single-gang version.
What do the contact terminal labels mean?
The relay has two changeover contact sets. In T2’s connection diagram, NO means normally open, C means common and NC means normally closed. Use the installation guide to identify the terminals for the circuit you are switching.
What does the LED indicate?
T2 describes the LED as indicating that the relay contacts are in the active position. Its wiring example also identifies the contacts that close when the monitored output is active.
Downloads
- Easy Relay 24V Fire Panel Relay (Adobe PDF)
Additional information
| Weight | 0.3 kg |
|---|