OSID beam detectors use optical imaging to detect smoke across open spaces. OSID stands for Open-area Smoke Imaging Detection. The range includes OSID-DE, with separate emitters and an imager, and OSID-R, which uses a reflector. Choosing the right system means checking the model, beam paths, distance and power arrangements together.
Updated 9 November 2026: reviewed against Xtralis’s current OSID information and international datasheet, with model-selection tables and an installation checklist added.
Jump to: how it works | detector comparison | OSI-10 and OSI-90 | planning checklist | products | FAQs
What is OSID, and who makes it?
OSID is part of Xtralis’s smoke-detection range. It is intended for open-area applications such as atria, warehouses, halls and other large spaces where the detection layout and access for installation or maintenance need careful consideration. The Xtralis OSID range overview distinguishes the dual-ended and reflective systems.
OSID is a form of projected-beam detection. A point smoke detector detects smoke entering its own sensing chamber; a beam detector measures the effect of smoke along an optical path across the protected space. Neither approach is a universal replacement for the other: the fire strategy, smoke movement, building layout and applicable design requirements determine the suitable method.
How does an OSID beam detector work?
In an OSID-DE system, an emitter sends coded ultraviolet and infrared light towards an imager on the opposite side of the space. The imager analyses the received light to measure smoke obscuration. It also monitors the emitter signals, so a missing emitter or one outside its field of view can produce a fault condition.
Dual-wavelength particle detection
The two wavelengths respond differently to particles. Xtralis uses that difference to help OSID-DE distinguish smoke from transient dust and solid objects, reducing nuisance alarms. This is a discrimination feature, not permission to ignore persistent dust, steam, obstructions or unsuitable conditions.
Optical imaging and building movement
The CMOS imaging sensor locates and tracks the emitters within its field of view. This gives tolerance to alignment drift caused by building movement. Initial alignment and suitable mounting are still needed; “no precise alignment” does not mean that an emitter can be placed anywhere or that the system needs no commissioning. See Xtralis’s OSID-DE information.
OSID-DE, OSID-R and other smoke detectors compared
| Approach | How it detects smoke | What to consider |
|---|---|---|
| Optical point smoke detector | Smoke enters the detector’s local sensing chamber. | The detector layout and access to each unit must suit the premises. It does not measure smoke along a beam across the room. |
| Conventional projected-beam detector | Typically measures the reduction of infrared light along an open path; reflective models return the beam to the same head. | Check the exact head/reflector arrangement, clear sight line, mounting and model-specific range. |
| OSID-DE | A separate emitter sends coded UV and IR light to a CMOS imager. Selected configurations support multiple emitters. | Choose the imager and emitter combination for the distance and viewing angles. Plan power and access at both ends. |
| OSID-R | A combined transmitter/receiver uses a reflector and a single infrared wavelength. | Power and connectivity are at the detector head. Do not apply OSID-DE emitter counts or dual-wavelength claims to this system. |
The comparison draws on Xtralis’s OSID explanation, the OSID-R product information, Hochiki’s projected-beam operating principle and Apollo’s optical point-detector description. It compares technologies, not universal suitability or interchangeable products.
OSI-10 or OSI-90: which imager do you need?
The OSID-DE imagers currently offered on Huvo are OSI-10 and OSI-90. The numbers are model names: Xtralis lists horizontal fields of view of 7° and 80° respectively. Huvo’s Coverage selector uses those field-of-view values.
| Imager | Horizontal field of view | Published standard-power distance | Maximum emitters |
|---|---|---|---|
| OSI-10 | 7° | 30–150 m | 1 |
| OSI-90 | 80° | 6–34 m; maximum measured at the centre of the field of view | 7 |
These figures come from the EN54-12 configuration table in the international datasheet linked under Resources on Xtralis’s OSID-DE page. They are configuration limits, not a complete detection layout. Check the full imager/emitter combination, position within the field of view and the applicable approval before specifying. High-power emitters have different distance limits and approval-specific restrictions; do not apply a headline maximum distance to every combination.
An OSI-90 can use emitters at different positions or heights within an approved design. Its seven-emitter capacity does not mean every installation needs seven, or that one imager automatically covers an entire warehouse. An OSI-10 is the single-emitter option.
Choose the emitter power option as well as the imager
| Emitter | Power level | Supply choice |
|---|---|---|
| OSE-SP-01 | Standard power | Battery operated |
| OSE-SPW | Standard power | Wired |
| OSE-HP-01 | High power | Battery operated |
| OSE-HPW | High power | Wired |
Xtralis lists these references in its current datasheet. Battery-powered emitters can reduce wiring at the emitter position, but the imager still needs a suitable wired supply; the datasheet specifies 20–30 V DC for the imager. Check the required battery type, replacement arrangements and operating conditions for the chosen emitter. Do not treat battery life as an unconditional site guarantee.
OSID specification and installation checklist
- Confirm the system family. Record OSID-DE or OSID-R and the exact model references; emitter and reflector systems have different layouts.
- Measure the optical paths. Check actual imager-to-emitter distances, viewing angles and planned detection positions against the manufacturer’s configuration information.
- Check changing obstructions. Consider racking, stored goods, signs, doors, cranes and future layout changes that could interrupt the sight lines.
- Assess the environment. Review dust, steam, condensation, lighting and building movement. Select suitable housings or other measures where the design calls for them.
- Plan power and panel connections. Include the imager supply, each emitter’s supply choice, alarm/fault interfaces and compatibility with the receiving fire alarm system.
- Plan safe access. Allow for alignment, commissioning, cleaning, battery replacement and future testing at all relevant positions.
- Commission to the manufacturer’s procedure. Confirm alignment, detection operation, fault reporting and the required panel response before handover.
- Keep the records. Retain the model schedule, settings, beam layout, test results and maintenance instructions for the installed system.
Installation, testing and maintenance
OSID-DE uses an alignment tool to aim the emitter towards the imager and set the imager’s field of view around its emitters. The OSP-002 laser alignment tool is an installation aid; the smoke-detection beam itself is LED-based. A laser tool and an imager on their own are not a complete detection system.
Xtralis’s datasheet describes cleaning of the optical faces and provides event-log diagnostics. Build maintenance around the installed equipment and conditions: keep optical paths clear, inspect contamination and mounting, check reported faults, and arrange the required functional tests and battery work with a competent maintainer. Use the current instructions for the exact models rather than treating “simple maintenance” as “maintenance-free”.
This checklist is a planning aid. It does not prescribe beam spacing, mounting height, sensitivity, test intervals or a complete compliant design. Those decisions need the applicable requirements, manufacturer instructions and a competent assessment of the premises.
OSID imagers and emitters available from Huvo
Use the cards below to select the model options. The imager and emitter are separate products. Confirm quantities, supply arrangements and the full design before ordering. Open the product details for the datasheet and model options.
For the imager, choose 7° for OSI-10 or 80° for OSI-90. Select the emitter separately by power level and wired/battery supply, using the references above.
Browse OSID equipment and accessories, or contact Huvo with the model references and project requirements.
OSID beam-detector FAQs
What does OSID stand for?
OSID means Open-area Smoke Imaging Detection. Xtralis uses the name for its imaging-based beam smoke-detection range, which includes dual-ended OSID-DE and reflective OSID-R.
Does every OSID detector use two wavelengths?
No. OSID-DE uses coded ultraviolet and infrared light from separate emitters. OSID-R uses a single infrared wavelength and a reflector. Check the family before applying specifications.
Can one OSID imager monitor seven emitters?
The OSI-90 supports up to seven emitters in a suitable configuration. The OSI-10 supports one. The allowable arrangement also depends on distances, angles and the manufacturer’s design requirements.
What is the range of OSI-10 and OSI-90?
With standard-power emitters, Xtralis’s EN54-12 table gives 30–150m for OSI-10 and 6–34m for OSI-90, with the latter maximum measured at the centre of its field of view. High-power configurations have different limits.
Is OSID completely battery powered?
Battery-operated emitters are available. The OSID-DE imager still requires a wired supply; battery emitters do not make the whole installation battery-only.
Can OSID ignore dust or blocked beams?
OSID-DE uses two wavelengths and imaging to help reject nuisance signals, but this does not remove the need to assess the environment or keep the optical paths clear. Investigate faults and follow the installed system’s maintenance instructions.