Key features

  • 24hr quiescent, 3hr full power battery backup
  • Expandable to four line cards for growth
  • Networkable via copper or fibre cabling

Downloads

Summary

The Baldwin Boxall OCCPS is the master control panel at the heart of an OmniCALL system, letting you run disabled refuge alarms, fire telephones, emergency/steward telephones and assistance alarms from a single addressable platform instead of wiring separate systems for each. That’s fewer control panels to specify, install and hand over on any given job.

View full overview Show less

For you, that means less time spent coordinating multiple wiring runs and equipment schedules on site, and a single point of commissioning and maintenance for the client afterwards. It’s designed to meet BS8893:2024 and designed for BS5839-9 compliance, giving you a documented basis for sign-off on emergency voice communication (EVC) installations.

The panel delivers this through a 5-inch colour TFT display with a customisable outstation layout and active call list, so operators can see and respond to calls at a glance. Loop and radial outstation wiring can be mixed on the same system, and additional line cards let you scale a single loop up to a full four-loop, 32-outstation configuration as the project demands.

Features

  • Loop and radial wiring on one system – mix cable topologies to suit existing containment and reduce rewiring on refurbishments
  • Expandable line cards – start with one loop or four radials and add up to three more line cards to reach 32 outstations without changing the master station
  • Separate assistance alarm indication – operators can immediately tell an assistance call apart from a refuge or telephone call on the display
  • Internal backup batteries – 24 hours quiescent and 3 hours full power keeps the system operational through a mains outage
  • 5-inch colour TFT display – customisable outstation layout and active call list speed up incident response for the operator
  • Networkable via copper or fibre – link multiple master stations across a building or site for larger or multi-block schemes
  • Fully monitored with self-describing faults – time and date stamped activity and fault logs simplify maintenance visits and compliance records
  • Up to 4-way conference calling – Type A/C outstations plus the operator can be joined on one call for coordinated incident handling
  • Paging option – broadcast to the loudspeaker of every occupied refuge outstation and telephone
  • Delayed call output and third-party interfacing – connect to remote lamp buzzers or other building systems as the specification requires

FAQ

Can one OCCPS panel handle both refuge outstations and disabled toilet alarms, or do they need separate systems?

The OCCPS supports both on the same master panel. Toilet and assistance alarms can be wired directly into a refuge outstation, with each call registering as its own address, or connected via a Baldwin Boxall interface unit (OCACIF) where that suits the installation better. A separate system is not required.


How do I add more outstations if the site grows?

The OCCPS ships with one line card fitted as standard, supporting one loop of up to 32 remotes or four radial circuits. Fitting up to three additional line cards extends this to four loops and a total of 32 outstations, distributed however the site layout requires.


What are the battery backup requirements, and how long will the system run during a power cut?

The OCCPS features internal backup batteries that provide 24 hours of quiescent standby operation followed by 3 hours of full power, ensuring the system remains operational during a standard mains failure.


Specifications

Product CodeOCCPS
Power Supply85-264VAC
Power Consumption75W
Humidity Range95% non-condensing
Temperature Range-5°C to +40°C
Indicators5″ TFT plus fault LEDs
FinishRAL 9005
Dimensions (W x H x D)430 x 430 x 190 mm
Bezel Dimensions470 x 470 mm
Bezel Cutout440 x 440 mm
Knockouts20mm x 30 (Top)
Maximum OutstationsUp to 32 outstations plus 32 assistance alarms
Loop LengthMax 1.4km, dependent on number of outstations
Radial LengthMax 1.4km shared between 4 outstations
Battery Backup24 hours quiescent, 3 hours full power
ComplianceDesigned to meet BS8893:2024, designed for BS5839-9 compliance