Gent Vigilon S4-34415 | Mains Rated Single Channel Interface | Output Only Unit
£100.80 (inc VAT: £120.96)
Summary
The Honeywell Gent S4-34415 is a loop powered single channel mains switching interface designed for fire detection and alarm systems. This device provides a reliable connection point between the Vigilon fire alarm control panel and external plant equipment or safety systems requiring mains voltage switching.
As a loop powered device, the S4-34415 eliminates the need for separate power cabling, reducing installation costs and complexity. Each interface is individually addressable on the loop, maximizing system information and enabling flexible cause and effect programming. The device comes complete with an integrated relay and protective enclosure, providing a ready-to-install solution for interfacing with critical building systems.
Certified to EN54-17 and EN54-18 standards, the S4-34415 features built-in short circuit handling for enhanced system integrity. It is compatible with Vigilon fire alarm panels and forms part of a comprehensive range of interface devices designed to simplify fire safety system design and installation.
Features
- Loop powered operation reducing installation and maintenance costs
- Single channel mains voltage switching output
- Individual loop addressing for maximum flexibility and control
- EN54-17 short circuit handling for enhanced system reliability
- Integrated relay for direct mains switching applications
- Complete with protective enclosure for simplified installation
- Compatible with Vigilon fire alarm control panels
- Output only configuration for plant control and system signaling
- Device load factor of 5 allows up to 200 devices per loop
- Operating temperature range from -25°C to +70°C
- DIN rail mounting option available with model S4-34411
- Certified to EN54-17:2005 and EN54-18:2005 standards
- LPCB approved for fire safety applications
- Suitable for connecting to sprinkler systems, HVAC controls, and emergency management systems
- IP40 protection rating in metal enclosure
FAQs
What is the S4-34415 used for?
The S4-34415 is a loop powered interface module used to connect Vigilon fire alarm systems to external mains-powered equipment. It provides a single channel switching output, typically used to control plant equipment, activate emergency systems like sprinklers, or signal other building management systems in the event of a fire alarm.
Does the S4-34415 come with an enclosure?
Yes, the S4-34415 comes complete with a relay and protective enclosure, providing a ready-to-install solution. The enclosure provides IP40 protection and houses all necessary components.
What is the difference between S4-34415 and S4-34411?
Both are single channel output only interfaces with relay. The S4-34415 comes with a standard enclosure, while the S4-34411 is designed for DIN rail mounting, offering more flexible installation options in equipment cabinets or distribution boards.
How many S4-34415 interfaces can be connected to one loop?
With a device load factor of 5, up to 200 S4-34415 interfaces can theoretically be connected to a single loop, though the actual number will depend on the total load of all devices on the loop and the panel’s capacity.
Does the S4-34415 require separate power supply?
No, the S4-34415 is loop powered, meaning it draws its operating power directly from the fire alarm loop. This eliminates the need for separate power cabling, reducing installation costs and complexity.
What voltage can the relay switch?
The S4-34415 is designed for mains voltage switching applications, though specific voltage and current ratings should be confirmed with the manufacturer or detailed technical documentation for your particular application requirements.
Is the S4-34415 certified for use in fire alarm systems?
Yes, the S4-34415 is certified to EN54-17:2005 and EN54-18:2005 standards and is LPCB approved, making it suitable for use in commercial fire detection and alarm systems.
What fire alarm panels is the S4-34415 compatible with?
The S4-34415 is compatible with Vigilon fire alarm control panels running Loop firmware V3.93/V4.35 or later and Main Control Card firmware V3.94/V4.37 or later.
Can I use the S4-34415 outdoors?
The S4-34415 with its standard enclosure has an IP40 protection rating, which is suitable for indoor use only. For outdoor applications, additional weatherproof enclosures would be required.
What happens if the loop is short-circuited?
The S4-34415 features EN54-17 compliant short circuit handling, which means the device is designed to isolate faults and maintain system integrity even in the event of a short circuit on the loop.
Specifications
- Model: S4-34415
- Type: Single channel mains switching interface (output only)
- Power Source: Loop powered
- Channels: 1 output
- Relay Included: Yes
- Enclosure Included: Yes
- Approximate Weight: PCB with cover in metal box: 800g
- Operating Temperature: -25°C to +70°C
- Relative Humidity: Up to 95% at +5°C to +45°C (non-condensing)
- Ingress Protection: IP40 (metal box, estimated)
- Device Load Factor: 5 (maximum 200 devices per loop)
- Panel Compatibility: Vigilon panels with Loop V3.93/V4.35 or later and Main Control Card V3.94/V4.37 or later
- Certification: EN54-17:2005 and EN54-18:2005
- Approval: LPCB
- Mounting: Wall mount with enclosure
- Alternative Model: S4-34411 (DIN rail mounting version)
Downloads
- Datasheet (Adobe PDF)
Additional information
| System Type | |
|---|---|
| Device Type | |
| Protocol |