Shopping Basket

0 Items

Subtotal £0.00

Haydon

Haydon HAY-FIRE-24R 24V Fire Relay | Double Pole, 5A @ 250V AC

£11.71 (inc VAT: £14.05)

Low Stock

SKU: HAY-FIRE-24R Category: Brand:

You may also need

  • Haydon HAY-FIRE-DO | Remote LED Fire Detector Indicator | Dual Voltage, Single Gang Compatible

    Haydon HAY-FIRE-DO

    SKU: HAY-FIRE-DO

    Low Stock

    £2.69 (inc VAT: £3.23)
    Add

Key features

  • Surface back box supplied
  • 22mA nominal current consumption
  • Faceplate indicator shows relay operated

Downloads

Summary

The Haydon HAY-FIRE-24R is a 24V DC fire relay for switching auxiliary equipment from your fire alarm system, with double pole contacts rated at 5A @ 250V AC. That gives you two switched poles from a single 24V DC signal, in one boxed unit.

View full overview Show less

It arrives with its own surface back box, so you are not sourcing a separate enclosure or pattress for the job. The 86mm x 86mm faceplate is marked “Auxiliary Relay Operated” and carries a red indicator, so you and the end user can see the relay’s state at a glance during commissioning and routine testing.

The coil draws a nominal 22mA at 24V DC, which keeps the load on the supply modest and makes it simple to account for in your standby battery calculations.

Features

  • Double pole relay – two switched poles from one 24V DC signal
  • 5A @ 250V AC contact rating – headroom for switching mains-rated auxiliary loads within the stated limit
  • Surface back box supplied – no separate enclosure to source, so the unit is ready to mount
  • Marked faceplate with indicator – “Auxiliary Relay Operated” legend and red indicator make the relay’s state easy to identify on site
  • 22mA nominal current consumption – a modest, known load for your supply and battery calculations
  • Standard 86mm x 86mm footprint – a familiar single gang size that sits neatly alongside other wall-mounted accessories
  • 3 year warranty – manufacturer cover for peace of mind after handover

Specifications

Operating Voltage24V DC + 10%
Nominal Current Consumption22mA
RelayDouble pole
Relay Rating5A @ 250V AC
Relay Coil Impedance1067 Ohms
Enclosure MaterialPlastic
DimensionsW 86mm x L 86mm x H 62mm (faceplate)
Back BoxSurface back box supplied
Weight0.2kg
Warranty3 years
ApprovalsUKCA, CE, FCC, RoHS

FAQ

What supply does the HAY-FIRE-24R need?

It is a 24V DC device, with the datasheet giving a 10% tolerance on that operating voltage. It is not specified for 12V systems, so use it only where a 24V DC signal or supply is available. Allow for its 22mA nominal current when you work out panel loading and standby battery capacity.


Do I need to buy a back box separately?

No. A surface back box is supplied with the relay, so it is ready to fix straight to the surface. Allow for an overall depth of 62mm with the back box fitted.


Are the contacts changeover, normally open or normally closed?

The datasheet confirms a double pole relay rated at 5A @ 250V AC but does not state the contact arrangement. If your application depends on a specific arrangement, confirm it with Haydon or check the terminal markings on the unit before you design it in.


Can I connect it directly to a monitored sounder circuit?

The datasheet does not say whether the coil is polarised or suppressed, which is what you would need to know before connecting any relay across a monitored circuit. Confirm this with Haydon first, or drive the relay from a suitable 24V DC auxiliary output instead.


How do I know the relay has operated?

The faceplate is marked “Auxiliary Relay Operated” and has a red indicator in the centre. This gives you a visual reference at the unit itself, which is useful when you are testing cause and effect during commissioning.


Downloads

Additional information

Colour

Mounting

Surface

Enclosure

Trigger Voltage

24V

Voltage

24V DC

Unit

Single

Trade
Account
Enquiry?