Hochiki

Hochiki CHQ-POM ESP Intelligent Powered Output Module | User-Selectable 2-32mA Output, Two Monitored Inputs

£26.65 (inc VAT: £31.98)

In Stock

You may also need

  • Hochiki SMB-1 | Module Enclosure | IP66, 32 Knock-Outs

    Low Stock

    £23.75 (inc VAT: £28.50)
    Add

Key features

  • User-selectable output, 2-32mA in 2mA steps
  • Two monitored inputs built in
  • Colour-coded flying leads speed up wiring

Downloads

Summary

The Hochiki CHQ-POM is an intelligent powered output module built to supply third-party devices from the ESP loop, with a user-selectable output from 2 to 32 mA in 2 mA steps so you can match the exact current draw of the equipment you’re connecting rather than over or undersizing the circuit.

View full overview Show less

That selectable range means you’re not carrying multiple fixed-output modules for different third-party kit – one CHQ-POM covers a spread of current requirements, cutting the number of part numbers you need to stock for a job. It also includes two monitored inputs, giving it a wider role on site than Hochiki’s sounder and base products in the ESP range, which are built purely for audible output rather than input monitoring.

On site, the module’s small footprint lets you fit it alongside devices such as the IFD-E, and its colour-coded flying leads make the termination straightforward during first fix. Just remember it needs to sit next to the Type 1 detection device it’s serving, with no transmission path in between.

Features

  • Selectable current output – set 2-32mA in 2mA increments to match the third-party device’s actual power draw
  • Two monitored inputs – watch extra circuits without fitting a separate monitoring module
  • Compact enclosure – small enough to mount alongside third-party devices like the IFD-E
  • Colour-coded flying leads – makes termination quicker and reduces wiring mistakes on site
  • Digital ESP communication – integrates into the loop alongside other ESP devices

FAQ

What is the CHQ-POM actually for?

It’s a powered output module that supplies 24V DC to third-party equipment connected to an ESP loop, such as the IFD-E, while also giving you two monitored inputs on the same small unit. It’s not a detector or sounder itself – it’s an interface device.


Where do I need to mount it?

The module must be installed next to the Type 1 detection device it’s serving, with no transmission path between them. Plan your containment and cable runs with this in mind before first fix.


How do I set the output current?

The output is user-selectable across 2 to 32mA in 2mA steps, letting you set it to suit the connected device’s current requirement. The datasheet doesn’t detail the exact selection mechanism, so check the installation manual on site if you’re unsure.


Can the monitored inputs be used for standard detection circuits?

Yes, the two inputs are designed to be monitored and come with EOL resistors for normal state and input activation states, so they can supervise external circuits in the usual way. Check the input ratings in the specification table against the circuit you’re monitoring before wiring in.


What's the quiescent current draw I need to allow for on the loop?

The module draws a typical quiescent current of 200 μA at 41V, which you should factor into your loop power budget alongside its alarm current of 2.3 to 32.3mA when the output is active.


What cable sizes do the flying leads suit?

The datasheet doesn’t specify a cable gauge for the flying leads, so confirm compatible cable sizes with the installation documentation or Hochiki technical support before ordering terminals.


Specifications

Ordering CodeCHQ-POM
Operating Voltage17-31 VDC
Transmission MethodDigital communication using ESP
Quiescent Current (Typ)200 μA (@ 41V)
Alarm Current2.3-32.3 mA
Test Signal Voltage14-30 VDC
Input Ratings – Open Circuit> 100 KΩ
Input Ratings – Normal State100 KΩ (EOL resistor provided)
Input Ratings – Input Activation470 KΩ (EOL resistor provided)
Input Ratings – Short Circuit50 KΩ
Operating Temperature Range-10°C to +50°C
Storage Temperature Range-30°C to +60°C
Maximum Humidity95% RH, non-condensing (at 40°C)
ColourIvory
Case MaterialACS
Weight30g
DimensionsL 30 x W 42 x D 19 mm

Downloads

Additional information

Weight0.1 kg
Device Type

Environment

Protocol

System Type