Quantec Addressable Call Point, Button Reset with Iconised Label & Remote Socket
£38.19 (inc VAT: £45.83)
Summary
The C-TEC Quantec QT602E is a programmable addressable call point designed for use with C-TEC’s Quantec Addressable Call System. This versatile device features an iconised call button, reset button and red/green confidence light, providing clear visual feedback for staff and residents in healthcare and assisted living environments.
The call point can be configured to make up to five levels of call including Standard, Ensuite, Help Required, Emergency, and Presence & Attendance, depending on configuration and connected ancillary devices. When connected to a compatible infrared receiver, the unit can also facilitate Attack and Attendance calls, providing comprehensive emergency response capabilities.
With its built-in remote socket and expansion connections, the QT602E offers exceptional flexibility. The onboard 6.35mm remote jack socket allows the optional connection of tail call leads, pressure mats and movement detectors, whilst dedicated expansion terminals enable the connection of dummy/extender devices including overdoor lights, additional call points, ceiling pulls and infrared receivers. Programming is achieved using a QT423 configurator, allowing the call point to operate in a multitude of ways to suit specific installation requirements.
Features
- Programmable addressable call point for C-TEC Quantec Addressable Call System
- Iconised call button and reset button with red/green confidence LED indicator
- Supports up to 5 call levels: Standard, Ensuite, Help Required, Emergency, Presence & Attendance
- Attack and Attendance calls available when connected to compatible infrared receiver
- Onboard 6.35mm remote jack socket for tail call leads, pressure mats and movement detectors
- Expansion connections for ancillary devices including ceiling pulls, overdoor lights and infrared receivers
- Compatible with dummy/extender devices for flexible system configuration
- Programmable operation using QT423 configurator
- Low power consumption with less than 3mA quiescent current
- Compact design suitable for standard UK 25mm single gang back boxes
- IP20 rated plastic construction
- Operating temperature range from -5°C to +40°C
FAQ
What is the C-TEC Quantec QT602E call point used for?
The QT602E is a programmable addressable call point designed for nurse call and assisted living applications. It forms part of C-TEC’s Quantec Addressable Call System and enables residents or patients to summon assistance with different levels of urgency.
How many different types of call can the QT602E make?
The call point can make up to 5 levels of call depending on configuration and connected devices: Standard, Ensuite, Help Required, Emergency, and Presence & Attendance. Attack and Attendance calls are also possible when connected to a compatible infrared receiver.
What devices can be connected to the remote socket?
The onboard 6.35mm remote jack socket allows the connection of optional tail call leads (pear pushes), pressure mats and movement detectors, enabling flexible placement and activation options for users.
Can I expand the system with additional devices?
Yes, the QT602E features expansion connections (R, G, L+, SW, IR and SLV terminals) that allow the connection of dummy/extender overdoor lights, additional call points, ceiling pulls and infrared receivers.
How is the call point configured?
The QT602E is programmed using a QT423 configurator, which allows the call point to be set up to operate in various ways to suit specific installation requirements and user needs.
What type of back box is required for installation?
The call point can be mounted on a standard UK 25mm single gang flush or surface back box, making installation straightforward using common electrical accessories.
What power supply does the call point require?
The QT602E is powered by a nominal 24V DC supply provided by the Quantec Controller/Network. It has a low quiescent current of less than 3mA and an alarm current of 14mA.
Specifications
- Power Requirements: Nominal 24V DC (from Quantec Controller/Network)
- Quiescent Current: Less than 3mA
- Alarm Current: 14mA
- Indicators: Red/green confidence LED
- Controls: Iconised Call button; Iconised Reset button
- Connections: Net +: Net -; R; G; L+; SW; IR; SLV
- Expansion Connections: R; G; L+; SW; IR & SLV terminals allow the connection of optional dummy/extender overdoor lights, dummy/extender call points, dummy/extender ceiling pulls and dummy/extender infrared receivers
- Onboard 6.35mm Remote Jack Socket: Yes – for the optional connection of tail call leads/pear pushes, pressure mats and movement detectors
- Onboard Sounder: No
- Onboard Infrared Receiver: No
- Product Dimensions (mm): 86 W x 86 H x 30 D mm. Can be mounted on a standard UK 25mm single gang flush or surface back box
- Construction & Finish: Plastic
- IP Rating: IP20
- Weight: 72g
- Operating Conditions/Temperature: -5ºC to +40ºC. Max relative humidity: 95%