Quantec Display Interface
£76.63 (inc VAT: £91.96)
Summary
The Quantec Display Interface QT615S provides a seamless connection solution for integrating QT608CD1S large corridor displays into Quantec fire alarm systems. This interface module enables communication via an RS232 serial interface lead, which is supplied with the large display unit.
Designed for straightforward installation, the QT615S mounts on a standard UK 20mm double gang flush or surface back box, making it compatible with existing electrical infrastructure. The unit features intelligent connection monitoring that tracks the status of the large display, ensuring system integrity by reporting the interface as “Missing” on the Quantec controller if the display is disconnected or powered off.
Features
- Connects QT608CD1S large corridor display to Quantec systems via RS232 serial interface
- Mounts on standard UK 20mm double gang flush or surface back box
- Monitors data connection to large display
- Reports as “Missing” on Quantec controller if display is disconnected or switched off
- Low power consumption at less than 5mA quiescent current
- Compact design at 147 x 86 x 23mm
- IP41 rated plastic construction
- Operates in temperatures from -5°C to +40°C
FAQ
What displays are compatible with the QT615S interface?
The QT615S is specifically designed to connect the QT608CD1S large corridor display to Quantec fire alarm systems via RS232 serial interface.
What type of back box is required for installation?
The QT615S mounts on a standard UK 20mm double gang flush or surface back box with a minimum depth of 35mm.
Does the interface require separate power supply?
No, the QT615S is powered directly from the Quantec Controller or Network at nominal 24V DC, drawing less than 5mA quiescent current.
How does the system know if the display is disconnected?
The QT615S continuously monitors the data connection to the large display. If this connection is interrupted or the display is switched off, the interface will appear as “Missing” on the Quantec controller, alerting system operators to the issue.
Can I control the display through this interface?
The QT615S has no built-in controls. If control functions are required, a QT608C display should be used instead.
What are the environmental operating limits?
The QT615S operates in temperatures ranging from -5°C to +40°C with maximum relative humidity of 95%, making it suitable for most indoor fire alarm system installations.
Specifications
- Power Requirements: Nominal 24V DC (from Quantec Controller/Network)
- Quiescent Current: Less than 5mA
- Indicators: None
- Controls: None (use QT608C display if controls required)
- Connections: Net +, Net -, RS232 serial port
- Product Dimensions: 147mm W x 86mm H x 23mm D (mounts on 35mm deep double gang back box)
- Construction & Finish: Plastic
- IP Rating: IP41
- Weight: 260g
- Operating Conditions/Temperature: -5°C to +40°C, maximum relative humidity 95%