Advanced MxPro 5 – 2 Loop Panel
Key features
- Expandable from 1 to 2 loops
- Advanced graphical LCD user interface
- Compatible with AdvancedLive for secure monitoring
Downloads
Summary
For an Advanced MxPro 5 two-loop panel, select 2 under Loops. The medium Apollo or Hochiki version is MX-5202 with two loops fitted or MX-5201 with one loop fitted. Choose the device protocol specified for your system and the enclosure size you need.
View full overview Show less
Which MxPro 5 panel do I need?
| Device compatibility | Enclosure | 1 loop fitted | 2 loops fitted |
|---|---|---|---|
| Apollo or Hochiki | Medium | MX-5201 | MX-5202 |
| Apollo or Hochiki | Large | MX-5201L | MX-5202L |
| Apollo or Hochiki | Deep | MX-5201D | MX-5202D |
| Argus Vega | Medium | MX-5201V | MX-5202V |
| Argus Vega | Large | MX-5201VL | MX-5202VL |
| Argus Vega | Deep | MX-5201VD | MX-5202VD |
| Nittan Evolution | Medium | MX-5201N | MX-5202N |
| Nittan Evolution | Large | MX-5201NL | MX-5202NL |
| Nittan Evolution | Deep | MX-5201ND | MX-5202ND |
See the Advanced MxPro 5 ordering guide for the full range. These panels have two onboard sounder circuits, 20 programmable zone LEDs and a graphical LCD.
With compatibility for AdvancedLive (UK&I only), the MxPro 5 series enables secure, real-time management of fire systems. Its powerful programming capabilities and enhanced diagnostics make it suitable for a variety of applications, from small installations to large, complex multi-area systems. The user-friendly interface and extensive software suite further enhance the operational experience.
Key Features
- 2 onboard sounder circuits and 20 programmable zonal LEDs
- 25 system LEDs for information purposes
- 4 programmable function buttons with LED indication
- Powerful cause-and-effect programming and enhanced trace diagnostics
- Fully programmable via onboard alphanumeric keypad or PC software
- Dedicated USB and RS232 serial ports for direct PC or modem connection
- Installer-friendly auto-learn and loop detection features
- Robust removable equipment chassis with plug-in connectors
- Integral P-Bus for system expansion via available option cards
- Advanced networking capabilities with peer-to-peer system
- Global compliance and 3-year warranty
FAQ
How Can I Change The Company Logo On MXPro 5 Screen?
This can only be changed with the use of the PC-NET-007 logo software and programming lead.
Can I expand a one-loop MxPro 5 panel to two loops?
The MxPro 5 1–2 loop panel can be expanded to two loops. Choose the loop card for the specified protocol. Select 2 under Loops if you need both loops fitted when you order.
Would a single panel support different protocols on separate loop cards?
No, each panel will support a single protocol only.
Similarly does the MxPro 5 network support multiple panels each with different protocols?
Yes, panels on the network can each support different protocols.
Specifications
- Base Technology : Dual Flash-Based Processors With Real-Time Clock, Trace Diagnostics, Programmable Languages And Character Sets
- Display : White Backlit 240 X 64 Graphical LCD
- LED Indicators : 22 Red (1 X Fire, 1 X More Alarms, 20 X Zonal Programmable), 1 Green (Power), 13 Amber And 12 Bi-Colour (Fault & System)
- Controls : Alpha Numeric Keypad Permitting Navigation, Reset, Mute, Silence, Resound, Evacuate, And 4 X Programmable Push Buttons
- Protocols : Apollo (Soteria / XP95 / Discovery), Argus Vega, Hochiki ESP, Nittan Evolution
- Number Of Fire Zones : 2000 (200 Per Individual Panel)
- Number Of Loops : Dedicated 1-2 Loop Control Panel
- Loop Current : 500mA Per Loop
- On-Board Sounder Circuits : 2 X 1 Amp Programmable
- On-Board Relays : 2 X 1 Amp 30V AC/DC Programmable (10mA, 5V Min) – Expandable To 4 Using MXP-507
- Auxiliary Supply : 1 X 24V 500mA
- Programmable Input : 1 X Monitored Programmable Input On-Board
- Programmable Key Switch Inputs : 8 Volt Free Inputs
- Total Available Output Current : 5A Maximum Available For Loop Current + Sounder Outputs + Auxiliary Supply
- Mains Supply : 200 – 240V 50-60 Hz AC (+10%, -15% Tolerance) 1.4A Max
- Charger Current: 2A Temperature Compensated
- Ethernet : 10-Base-T, 100-Base-T Providing AdvancedLive Connectivity (UK&I Only)
- Serial Ports : 1 X On-Board RS232 Connection For PC, Modem, IP, Or Portable Printer
- USB Interface : 1 X USB B Type Connection For PC Communication
- Programming : On-Board Keypad Or PC Running Windows Tools
- Event Log : 5000 Event & Diagnostic + 500 Fire
- Networking : Optional Plug-In Network Card (MXP-503 – Standard, Or MXP-509 – Fault-Tolerant)
- Enclosure / Colour : Steel IP30 / RAL7035
- Assembled enclosure dimensions (H × W × D) : Medium (Standard) 345 × 430 × 120 mm, Large 475 × 450 × 120 mm, Deep (Large-Deep) 475 × 450 × 190 mm
Downloads
- Advanced 1–2 loop datasheet (Adobe PDF)
Additional information
| Weight | 10 kg |
|---|---|
| Device Compatibility | |
| Maximum Loops | |
| Loops | 1, 2 |
| Protocol | Hochiki ESP, Apollo, Argus Vega, Core, Discovery, Evolution, XP95 |
| Enclosure Size | |
| System Type | |
| Touchscreen | |
| Device Type |