Shopping Basket

0 Items

Subtotal £0.00

Patol Resettable Analogue Linear Heat Detection Cable

SKU: Patol-Resettable-Analogue-LHDC
SKU: Patol-Resettable-Analogue-LHDC Category: Brand:

Summary

The Patol Resettable Analogue Linear Heat Detection Cable (LHDC) is engineered to provide early detection of fire and overheating in environments where traditional detection methods are not feasible due to environmental constraints or cost. This cable is capable of monitoring extensive single zonal lengths and can trigger alarms for hot spots on small sections of the cable.

Constructed with a copper-coated steel central conductor, the cable features an inner insulation with a negative temperature coefficient (NTC), a tinned copper braid layer, and a flame retardant polyethylene (FRPE) sheath. The LHDC is used with an end of line functional unit and a zone monitoring unit or control panel equipped with an appropriate LHDC interface channel. It is suitable for hazardous areas when used with Intrinsically Safe Zener Barriers, and can be installed with interposing cables for remote monitoring.

Features

  • Low smoke zero halogen
  • Adjustable alarm set point
  • Recoverable and resettable operation
  • Can detect hot spots
  • Zones of up to 500m in length
  • Chemical resistant
  • Mechanical protection available
  • Easy to install
  • Compatible with a full range of monitoring devices
  • RoHS compliant – Lead Free

Specifications

  • Outer Sheath : Red Flame Retardant Polyethylene (FRPE) – Standard
  • Outer Diameter : Red FRPE: 3.3 mm ±10%
  • Minimum Operating Temperature : -20°C
  • Minimum Installation Temperature : 0°C
  • Weight 1km on the reel : Red FRPE: 19kg
  • Tensile Strength : 200 Newtons