Shopping Basket

0 Items

Subtotal £0.00

Kentec

Kentec Sigma CP Conventional 2, 4 or 8 Zone Panel

SKU: 037c6c8f35f7
SKU: 037c6c8f35f7 Categories: , Brand:

You may also need

Key features

  • BS EN 54-2 and BS EN 54-4 certified
  • 2, 4 or 8 conventional detection zones
  • Four-wire K-series panel with LCMU included

Downloads

Summary

The Kentec Sigma CP is a four-wire conventional fire alarm panel with 2, 4 or 8 detection zones. The KL-series versions on this listing include Kentec’s active end-of-line monitoring (LCMU). Detectors and call points connect to detection zones, while sounders use two separate monitored outputs.

View full overview Show less
Kentec Sigma CP order codes
ZonesKentec part number
2KL11020M2
4KL11040M2
8KL11080M2

All three have a 385 × 310 × 90 mm enclosure (W × H × D) and an integral mains power supply and battery charger.

Features

  • Fully certified to BS EN54-2 and BS EN54-4
  • 2, 4 or 8 conventional detection zones
  • Four-wire K-series variants with LCMU included
  • 2-wire repeaters and ancillary boards
  • Fully programmable using simple menu options
    • Adjustable sounder delay time
    • Sounder configuration options
    • Zonal sounder delay detectors only
    • Zonal sounder delay call points only
    • Coincidence input selection
    • I.S Barrier selection by zone
    • Short circuit fire by zone
    • Non latching zones
    • Silent zones
    • Zone input delay
    • General panel configuration
  • Simple, single board construction
  • Installer friendly
  • Compatible with wide range of detection devices
  • Two monitored sounder outputs
  • 3 Amp power supply
  • Auxiliary power output

FAQ

Which Kentec Sigma CP part number do I need?

Select 2 zones for KL11020M2, 4 zones for KL11040M2 or 8 zones for KL11080M2. All three are conventional four-wire panels with LCMU included.

Is this the Sav-Wire or AlarmSense panel?

This listing is for the standard four-wire Sigma CP. See the separate Sigma CP Sav-Wire or Sigma CP-A AlarmSense listing if your system uses either of those versions.

What end-of-line resistors does the four-wire Sigma CP use?

Kentec specifies 6.8 kΩ for passive detection zone monitoring and 10 kΩ for the dedicated sounder circuits. Follow the Kentec installation manual for when to use the included active LCMU in place of the detection-zone resistor.

Specifications

  • Construction : 1.2mm mild sheet steel
  • IP Rating : IP30
  • Finish : Epoxy powder coated
  • Colour – lid & box : BS 00 A 05 grey – fine texture
  • Colour – controls plate & labels : RAL 7047 light grey – satin
  • Weight : 6kg
  • Supply voltage : 230V AC (+10%/-15%)
  • Mains supply fuse : 1.6 Amp 250V
  • Power supply DC rating : 24V 3 Amps
  • Maximum battery size : 7Ah 12V (2 per panel)
  • Fault contact rating : 30V DC 1 Amp
  • Local fire contact rating : 30V DC 1 Amp
  • Fire contact rating : 30V DC 1 Amp
  • Sounder output rating : 500 mA fuse per output, 750 mA maximum combined across S1 and S2
  • Detection zone current : 1.6 milliamps
  • Detection zone EOL resistor : 6k8 5%
  • Active EOL : LCMU included with the KL models on this listing
  • Sounder output EOL resistor : 10k 5%
  • Cable capacity : 2.5mm² per terminal
  • Operating temperature : -5°C to +40°C
  • Operating humidity : <95% (non condensing)