Kentec Sigma CP Sav-Wire Two-Wire Fire Alarm Panel
Summary
The Kentec Sigma CP Sav-Wire Two-Wire Fire Alarm Panel is a conventional fire alarm control panel engineered for demanding fire detection and alarm system applications. Designed with ease of installation in mind, the two-wire configuration significantly reduces wiring complexity, making it an ideal choice for new installations and panel replacements on existing systems alike.
Available in 2, 4 and 8 zone configurations, the Sigma CP two-wire range offers flexibility to suit a wide variety of premises and project sizes. The panel is compatible with two-wire detector bases from leading manufacturers Apollo and Hochiki, as well as most standard conventional detectors, call points and sounders, ensuring broad compatibility across installations.
Fully certified to BS EN54-2 and BS EN54-4, and compatible with BS5839: Part 1: 2017 installations, the Sigma CP delivers reliable performance and regulatory compliance. Extensive programmable configuration options — stored in non-volatile memory — are accessible via an intuitive user interface, allowing engineers to tailor the system quickly and efficiently on site.
Key Features
- Fully certified to BS EN54-2 and BS EN54-4
- 2-wire in 2, 4 or 8 zones
- Compatible for use on BS5839: Part 1: 2002 installations
- 2-wire repeaters and ancillary boards
- Fully programmable using simple menu options
- Adjustable sounder delay time
- Sounder configuration options
- Zonal sounder delay detectors only
- Zonal sounder delay call points only
- Coincidence input selection
- I.S Barrier selection by zone
- Short circuit fire by zone
- Non latching zones Silent zones
- Zone input delay
- General panel configuration
- Simple, single board construction
- Installer friendly
- Compatible with wide range of detection devices
- Two monitored sounder outputs 3 Amp power supply
- Auxiliary power output
Specifications
- Construction: 1.2mm mild sheet steel
- IP Rating: IP30
- Finish: Epoxy powder coated
- Colour (Lid And Box): BS 00 A 05 grey – fine texture
- Colour (Control Panel And Labels): RAL 7047 light grey – satin
- Weight: 6kg
- Dimensions: 385 x 310 x 90mm
- Supply Voltage: 230V AC (+10%/-15%)
- Mains Supply Fuse: 1.6 Amp 250V
- Power Supply DC Rating: 24V 3 Amps
- Maximum Battery Size: 7Ah 12V (2 per panel)
- Fault Contract Rating: 30V DC 1 Amp
- Local Fire Contract Rating: 30V DC 1 Amp
- Fire Contract Rating: 30V DC 1 Amp
- Sounder Output Rating: 0.5A per output (max 1.6A over all outputs)
- Detection Zone Current: 1.6 milliamps
- Detection Zone EOL Resistor: 6k8 5%
- Sounder Output EOL Resistor: 10k 5%
- Cable Capacity: 2.5mm² per terminal
- Operating Temperature: -5°C to +40°C
- Operating Humidity: <95% (non condensing)
- Alarm Current (2 Zone): 0.15 Amps
- Alarm Current (4 Zone): 0.3 Amps
- Alarm Current (8 Zone): 0.63 Amps
- Standby Current (2 Zone): 0.065 Amps
- Standby Current (4 Zone): 0.075 Amps
- Standby Current (8 Zone): 0.093 Amps
- Certifications: BS EN54-2, BS EN54-4
Features
- Two-wire panel design reduces installation time and wiring costs
- Available in 2, 4 or 8 detection zones
- Compatible with BS5839: Part 1: 2017 installations
- Fully certified to BS EN54-2 and BS EN54-4
- Compatible with Apollo and Hochiki two-wire detector bases
- Compatible with a wide range of conventional detectors, call points and sounders
- Two monitored sounder outputs
- 3 Amp, 24V DC power supply
- Auxiliary power output
- Simple single board construction
- Fully programmable via intuitive menu-driven interface
- Configuration stored in non-volatile memory
- Adjustable sounder delay time
- Zonal sounder delay for detectors only or call points only
- Coincidence input selection
- IS barrier selection by zone
- Short circuit fire by zone
- Non-latching zones
- Silent zones
- Zone input delay
- Maximum battery size 7Ah 12V (2 per panel)
- Two-wire repeaters and ancillary boards available
FAQ
What is the difference between the two-wire and four-wire Sigma CP panels?
The two-wire (T-prefix) Sigma CP panels use a two-wire detection circuit, which simplifies wiring and reduces installation time and cable costs compared to standard four-wire panels. The two-wire versions are compatible with Apollo and Hochiki two-wire detector bases, making them particularly suited to installations where wiring efficiency is a priority.
How many detection zones are available?
The Sigma CP two-wire range is available in 2 zone (T11020M2), 4 zone (T11040M2) and 8 zone (T11080M2) variants, allowing you to select the appropriate panel for the size and complexity of your installation.
Is the Sigma CP two-wire panel certified to the relevant fire alarm standards?
Yes. All Sigma CP panels are fully certified to BS EN54-2 (Fire detection and fire alarm systems — Control and indicating equipment) and BS EN54-4 (Power supply equipment), and are compatible for use on BS5839: Part 1: 2017 installations.
What detectors and devices are compatible with the Sigma CP two-wire panel?
The Sigma CP two-wire panel is compatible with two-wire detector bases from Apollo and Hochiki, as well as most standard conventional detectors, call points and sounders. This broad compatibility makes it suitable for a wide range of fire detection system designs.
What are the alarm current ratings for the two-wire panels?
The alarm current ratings for the two-wire panels are: 0.15 Amps for the 2 zone model (T11020M2), 0.3 Amps for the 4 zone model (T11040M2), and 0.63 Amps for the 8 zone model (T11080M2).
What battery backup does the Sigma CP support?
The Sigma CP panel supports a maximum battery size of 7Ah 12V, with two batteries per panel, providing standby power in the event of a mains supply failure in accordance with fire alarm system requirements.
Downloads
- Datasheet (Adobe PDF)
Additional information
| Weight | 6 kg |
|---|---|
| Zones | 2, 4, 8 |
| Device Type |