Updated 2 November 2026. First published in September 2022, this guide now covers the nine wireless ranges listed in Huvo’s wireless fire alarm systems category. It also explains where older ranges need a different approach when sourcing replacement equipment.
Choosing a wireless fire alarm system starts with the building and the job: a new system, an extension to an existing panel, or replacement parts for an installation already in service. The manufacturer’s name is only part of that decision. The panel, radio equipment and device generation need to work together.

Dedicated wireless panel or hybrid system?
A dedicated wireless panel system communicates with its own compatible field devices by radio. A hybrid system brings wireless devices into a system through a wired loop, translator or interface. Both approaches can reduce field cabling, but “wireless” does not mean every component is cable-free: control equipment and some radio infrastructure still need the specified power and connections.
For a new installation, compare the complete equipment schedule. For an extension, identify the existing panel and protocol before choosing a range. For replacements, start with the exact part number and generation. Our wireless versus hardwired guide explains the wider installation considerations.
Wireless fire alarm ranges at a glance
| Range | System approach | First check |
|---|---|---|
| EMS SmartCell | Dedicated SmartCell wireless panel and devices | Fire-device capacity and any information devices |
| EDA Zerio Plus | Wireless panel system with signal-booster options | Panel size and surveyed booster locations |
| Ajax EN54 Line | Wireless fire system built around EN54 Fire Hub Jeweller | Compatible EN54 devices and hub power/backup requirements |
| EMS FireCell | Compatible control panel with radio hub and cluster infrastructure | Panel, hub and cluster configuration |
| Hochiki Ekho | Hybrid wireless range for Hochiki ESP systems | Panel compatibility and installer training |
| Apollo REACH | Apollo hybrid wireless range | Panel approval and the correct REACH interface |
| Eurotech Sygno-fi | Hybrid wireless range with translators and expanders | Interface type and exact equipment generation |
| Hyfire Static | Older HFW range with a manufacturer discontinuation notice | Exact replacement part and availability; Taurus is not backward compatible |
| Wi-Fyre | Transponder-based wireless equipment | Exact transponder version and connection method |
This is a starting point for comparing ranges. A radio survey, the required detection and alarm coverage, and the manufacturer’s instructions determine the final design and equipment quantities.
SmartCell from EMS
SmartCell provides a dedicated wireless control panel with compatible detectors, call points, sounders and other devices. EMS positions it for small to medium installations. The SC-11-1201-0001-99 panel datasheet specifies up to 64 wireless fire or information devices in total, with a maximum of 32 fire detection devices. That distinction matters when counting the equipment for a job.
Browse SmartCell equipment for the panel, devices and accessories. If the specification includes non-fire functions, our SmartCell information-device guide explains that separate part of the range.
Zerio Plus from Electro Detectors
EDA Zerio Plus is a wireless panel system with wireless and wired signal-booster options. EDA lists 8, 20 and 100-zone control panels and up to 240 devices per system. The manufacturer makes the initial radio survey a key part of design, including identifying where boosters should be installed.
Browse Zerio Plus panels and devices. For help preparing an order, read how Huvo’s Zerio Plus pre-programming service works and ask us about the scope for your project. Our earlier interview with Mark Tansey provides background on the range.
EN54 Line from Ajax Systems
Ajax EN54 Line centres on EN54 Fire Hub Jeweller, the control and indicating equipment for the fire system. It provides a touch display for status and control, with compatible wireless fire devices connected to it. Check the device compatibility list, the hub’s external power requirements and the specified backup battery when preparing the system.
Use the dedicated Ajax EN54 Line range when selecting commercial fire equipment. Check the exact device against Ajax’s EN54 Fire Hub documentation rather than choosing on the Ajax name alone.
FireCell from EMS
FireCell uses radio infrastructure to connect wireless field devices to a compatible control panel. EMS’s Radio Hub datasheet describes a hub connected to the panel’s loop, working with Radio Cluster Communicators to form the wireless network. Panel choice, loop capacity and the surveyed cluster layout therefore belong in the comparison alongside the detectors and sounders.
Browse EMS FireCell equipment and check the exact panel, hub and cluster combination before adding to an existing installation.
Ekho from Hochiki
Ekho is Hochiki’s hybrid wireless family for integration with its ESP intelligent hardwired systems. Translators connect the wireless side to the wired system, with expanders used to extend radio coverage. Hochiki requires formal Ekho training for design, installation and commissioning, so check that requirement when planning the project.
Browse Hochiki Ekho equipment. Confirm the panel and translator requirements for the installation rather than assuming equipment from another Hochiki wireless generation is interchangeable.
REACH from Apollo Fire
Apollo REACH is a hybrid wireless range that enables wireless detection to connect to Apollo hardwired loop systems. Apollo provides dedicated REACH survey and commissioning resources. For an extension, confirm the panel’s approval for the intended equipment and the correct interface before selecting field devices.
Browse Apollo REACH equipment. Apollo also identifies XPander as a separate, original hybrid wireless range; its relationship to REACH is covered below.
Sygno-fi from Eurotech
Sygno-fi is Eurotech’s hybrid wireless fire range. Its catalogue includes intelligent translators, a conventional expander, wireless detectors, call points and interface devices. Eurotech also lists enhanced translator and expander versions, making the exact interface and part number important when comparing equipment or extending a system.
Browse Sygno-fi equipment and establish the required panel connection and equipment generation before ordering.
Wi-Fyre
Wi-Fyre uses transponders to communicate with wireless field devices. The Universal Transponder with LCD Indication datasheet describes up to 30 mixed field devices per transponder, including detectors, call points, sounders and input/output devices. Check the exact transponder version and its connection requirements for the panel you are working on.
Huvo’s Wi-Fyre range currently lists a transponder, sounder/flasher and survey kit. For an existing installation, send us the part numbers so we can check the required equipment and availability.
Static from Hyfire: check legacy requirements
Hyfire’s HFW discontinuation notice includes Static and Dynamic products. It set June 2025 as the last-time purchase deadline and explicitly states that HFW and Taurus are distinct product lines that are not backward compatible. A Taurus device should therefore not be selected as a direct replacement for a Static device.
Huvo still lists Hyfire Static equipment. Treat this as an enquiry about the exact existing system and available parts, rather than assuming a complete new system can be supplied from those listings.
Taurus from Hyfire
Hyfire’s current wireless overview presents Taurus and Taurus Evolution. These provide context for a new Hyfire enquiry, but do not establish compatibility with an existing Static installation. If you are planning a transition, contact Huvo with the existing equipment details and project requirements so the appropriate route can be checked.
XPander from Apollo Fire
Apollo describes XPander as its original hybrid wireless range and presents it separately from REACH. If you are maintaining XPander equipment, use the exact device and interface documentation when checking replacements. Our Apollo brand range is a starting point for enquiries; the REACH category is a separate shopping route, not a replacement-parts list for XPander.
What to confirm before choosing a system
- The job: new installation, extension or replacement parts, with the existing panel and device references where relevant.
- The complete schedule: detection, call points, sounders, visual alarms and interfaces, plus room for the intended expansion.
- The radio survey: the building’s actual signal paths and the locations of translators, expanders or boosters.
- Power and maintenance: panel and infrastructure supplies, backup provision, device batteries and the required service arrangements.
- Compatibility and training: the approved panel/interface combination, exact product generation and any manufacturer training requirements.
Ask Huvo for help with range selection and compatibility, or browse all wireless fire alarm ranges. Share the panel make/model and existing part numbers for an extension, or the equipment schedule and radio survey for a new project.
Manufacturer references
The range distinctions above were checked against the following manufacturer pages and documents on 2 November 2026. The EMS and Wi-Fyre documents linked here are manufacturer datasheets hosted by Huvo. Refer to the instructions for the exact model and generation when preparing a specification.
- EMS SmartCell SC-11-1201-0001-99 datasheet
- EDA Zerio Plus overview and survey guidance
- Ajax EN54 Fire Hub Jeweller manual
- EMS FireCell Radio Hub datasheet
- Hochiki Ekho overview and translator and training guidance
- Apollo REACH and XPander overview and REACH survey resources
- Eurotech Sygno-fi catalogue
- Wi-Fyre Universal Transponder with LCD Indication datasheet
- Hyfire HFW discontinuation notice and current wireless range overview