Shopping Basket

0 Items

Subtotal £0.00

Hochiki

Hochiki CHQ-DIM2 Intelligent Addressable Dual Input Module | 2 Independent Inputs, Integral Short-Circuit Isolator

SKU: 1762b39791f8

You may also need

Key features

  • Two inputs, each NO or NC configurable
  • Integral short-circuit isolator saves a loop device
  • DIN-rail version for cabinet mounting

Downloads

Summary

The CHQ-DIM2(SCI) dual input module lets you pick up two volt-free contacts, such as a door switch and a sprinkler flow switch, from a single loop address, with each input independently configurable for normally open (NO) or normally closed (NC) operation.

View full overview Show less

That independence means you can cover two separate monitoring points on one device instead of running two single-input modules, cutting cable runs, loop addresses and the number of enclosures you need to fit and commission on site.

Both the standard and DIN-rail versions build in a short-circuit isolator (SCI), so you don’t need a separate isolator module to protect the loop from a cable fault. When your fire alarm control panel supports Enhanced mode, the module also adds resistive line monitoring on each input; if the panel doesn’t support it, the device falls back to Compatibility mode and the inputs are no longer monitored, so it’s worth checking panel compatibility before you specify it.

Features

  • Two independently configurable inputs - monitor NO or NC contacts such as door switches, sprinkler flow switches or plant equipment from a single device
  • Integral short-circuit isolator - protects the loop without fitting a separate isolator module, saving space and parts
  • Enhanced mode resistive monitoring - gives full line monitoring on each input when the panel supports it, rather than a simple on/off signal
  • DIN-rail version (CHQ-DIM2/DIN(SCI)) - fits straight into a cabinet or plant room enclosure
  • Optional CHQ-BACKBOX - raises the enclosure to IP65 for damp or exposed mounting locations
  • LPCB approved, with a SIL level 2 approved variant available - supports higher-integrity system specifications

Specifications

Ordering CodeCHQ-DIM2(SCI) - Module / CHQ-DIM2/DIN(SCI) - DIN Module
Operating Voltage17 - 41 VDC
Quiescent Current (typ)280 µA
Current Consumption22 mA ±20% (polling), 4.3 mA (both inputs active); add 85 µA per input for NC contact monitoring
Current In Short Circuit8 mA
Max Short-Circuit Current (Loop)1 A
Input Line ResistanceON threshold <50 Ω, OFF threshold >100 KΩ
Operating Temperature Range-10°C to +50°C
Storage Temperature Range-30°C to +60°C
Max Humidity95% RH, non-condensing (at 40°C)
Weight - CHQ-DIM2(SCI)327 g (+235 g with lid and backbox)
Dimensions - CHQ-DIM2(SCI)With lid: L 157 x W 127 x D 35 mm; with lid and backbox: D 79 mm
Weight - CHQ-DIM2/DIN(SCI)113 g
Dimensions - CHQ-DIM2/DIN(SCI)L 108 x W 119 x D 24 mm
ApprovalsLPCB approved; SIL level 2 approved variant available

FAQ

Will this module monitor my sprinkler flow switch correctly?

Yes, it’s designed for exactly that kind of application, along with door contacts and plant equipment. Configure the relevant input as NO or NC to match the contact type you’re wiring in.


What happens if my fire alarm panel doesn't support Enhanced mode?

The module regresses into Compatibility mode, where the inputs are no longer monitored for line faults. Check with the panel manufacturer or your Hochiki documentation before relying on resistive monitoring for a project.


Can I mount this inside a control panel cabinet rather than on a wall?

Yes, the CHQ-DIM2/DIN(SCI) version is designed for DIN-rail mounting, making it a better fit for a plant room cabinet or panel enclosure than the standard enclosed version.


Do I need the back box for every installation?

Only where you need a higher ingress protection rating; fitting the CHQ-BACKBOX with the standard module raises it to IP65, which suits damp or exposed locations. For a dry indoor cabinet it isn’t necessary.


Where can I position this module relative to detectors?

On systems approved to EN54-13, it must be installed next to any Type 1 detection device, with no transmission path between them. Plan your containment layout with this in mind before first fix.


How much current does it draw from the loop?

Quiescent current is 280 µA, rising to around 22 mA ±20% during polling and 4.3 mA when both inputs are active; add 85 µA per input if you’re monitoring NC contacts. Factor this into your loop budget alongside your other loop devices.


Downloads

Additional information

Weight0.1 kg
Version

DIN Rail, Standard

Device Type

Environment

Protocol

System Type

Short Circuit Isolator