Apollo Discovery Optical Smoke Detector
£35.81 (inc VAT: £42.97)
Key features
- Addressable optical smoke detector, Apollo part 58000-600APO
- Five EN 54-approved response modes and drift compensation
- Discovery protocol with compatible XP95 and CoreProtocol panel support
Downloads
Summary
The Apollo Discovery 58000-600APO is an addressable optical smoke detector designed to respond to smoke from slow-burning and smouldering fires. Huvo lists the detector under SKU 58000-600. The mounting base is ordered separately.
View full overview Show less
The detector has five EN 54-approved response modes and drift compensation. It uses Discovery protocol and can operate on compatible XP95 and CoreProtocol systems. Confirm the exact detector and supported features with your fire panel manufacturer.
Features
- Photo-electric detection using infrared light scatter principle
- Responds exceptionally well to slow burning and smouldering fires
- Five EN54 approved response modes with selectable sensitivity levels
- Discovery protocol with XP95 and CoreProtocol compatibility subject to panel support
- Electrical remote test on supported panels
- Drift compensation technology maintains consistent sensitivity
- Rejection of transient signals reduces false alarm occurrences
- Unaffected by wind or atmospheric pressure changes
- Two integral 360° viewable LED indicators with optional remote LED
- Flashing LED mode programmable for polling indication
- Wide operating temperature range from -40°C to +70°C
- Compact 100mm diameter design with wind-resistant smoke inlets
- White flame-retardant polycarbonate housing
- Two-wire supply connection with polarity insensitive terminals
FAQ
Is 58000-600 the same part as 58000-600APO?
Yes. Apollo lists this Discovery Optical Smoke Detector as 58000-600APO on its product page and 58000-600 in datasheet PP2606.
Does the detector include a base?
The mounting base is ordered separately. Apollo shows the detector with an XPERT 7 mounting base in PP2606. Check the base and panel compatibility for your installation.
Will it work on an XP95 or CoreProtocol loop?
Apollo lists XP95 and CoreProtocol compatibility. Check the fire panel manufacturer’s documentation for support for this detector and features such as mode selection and remote testing.
What does the remote test check?
A supported panel can command the detector to simulate an alarm electrically. This confirms the electrical response. Follow the applicable maintenance instructions for functional testing.
What supply does the detector use?
It uses a two-wire addressable loop supplied at 17–28 V DC. For standby current and loop calculations, see the source figures in Specifications.
Specifications
- Part Number: 58000-600APO (Huvo SKU 58000-600)
- Detection Principle: Photo-electric detection of light scattered in forward direction by smoke particles
- Chamber Configuration: Horizontal optical bench housing infrared emitter and sensor arranged radially
- Sensor Type: Silicon PIN photo-diode
- Emitter Type: GaAlAs infrared light emitting diode
- Sampling Frequency: Once per second
- Digital Communication: Discovery protocol, with XP95 and CoreProtocol compatibility subject to panel support
- Modulation Voltage: 5-9V peak to peak
- Operating Voltage: 17V – 28V DC
- Quiescent current: Apollo’s PP2606 Issue 4 datasheet gives 300 µA typical (24 V DC, 25 °C, 50% RH). Apollo’s exact-model product page lists 440 µA at 24 V DC. Confirm the applicable figure with Apollo or the panel manufacturer before sizing the loop.
- Power-up Surge Current: 1mA
- Maximum Power-up Time: 10 seconds
- Alarm Current LED Illuminated: 3.5mA
- Clean-air Analogue Value: 23 +4/-0
- Alarm Level Analogue Value: 55
- Operating Temperature: -40°C to +70°C
- Storage Temperature: -40°C to +80°C
- Humidity Range: 0% to 95% RH (no condensation or icing)
- Dimensions: 100mm diameter x 42mm height (50mm height with XPERT 7 base)
- Weight: 105g (160g with XPERT 7 mounting base)
- Housing Material: White flame-retardant polycarbonate
- Terminal Material: Nickel plated stainless steel
- Standards And Approvals: EN 54-7, CPR, LPCB, VdS, BOSEC, SBSC and FG, as listed by Apollo
- Response Modes: Five EN54 approved modes with alarm thresholds from 1.4%/m to 2.4%/m
- Remote Output Characteristics: Connects to positive line through 4.5kΩ (5mA maximum)
- Alarm Indicator: Two clear 360° viewable LEDs illuminating red in alarm